elmeasure LG 64 Series Programming Manual Download Page 2

Frequency selection  

nor (Normal)/dISt (Distortion)

3.5 Enabling and Disabling Auto Scrolling 

Press        

for 5 Secs. Display shows :                      Again press 

 

 Down

 key 

down

key to disable. Display shows :

Starting Voltage
(V.SUP)

Starting Current
(A.SUP)

0.02% to 10.00% of FS

10V - 40V

Parameter 1 
selection 

( )

1

bASC/

/

thd/Vrh.E/Enr.E VAr/EnrG

POWr (Only for 6425,6435,6445)

Parameter 2 
selection 

( )

2

bASC/

/

thd/Vrh.E/Enr.E VAr/EnrG

POWr (Only for 6425,6435,6445)

Parameter   

3

selection 

(3)

bASC/

/

thd/Vrh.E/Enr.E VAr/EnrG

POWr (Only for 6435,6445)

Parameter   

4

selection 

(4)

bASC/

/

thd/Vrh.E/Enr.E VAr/EnrG

POWr (Only for 6445)

Bar graph 

A/VA/WAtS

3.6 Entering and Exit for Old Parameter 

Press        

for 5 Secs. Display shows :                      Again press 

 

 Up

 key 

up key for

5 Secs to exit.Display shows :

Dimension Bezel: 

 96 x 96 mm

  

(Depth 30/ 6mm behind Bezel)

4

Panel Cutout:

90    × 90     mm

+2

-0

+2

-0

41

96

90

90

96

90

+2
-0

90

+2
-0

30

46

96

90

90

96

57

90

+2
-0

90

+2
-0

No of Poles(POLES) 

2  - 28 poles

Demand Period 

( )

5

1 - 30 (Only for 6400)

Single phase Connection 

5VA

AUX

V1, V2, V3

 

PT  (optional)

V1

VN

RS485

+

+

Load 

Line 

Delta Connection (2E)  3 Phase 3 Wire system 

Star Connection (3E) 3 Phase 4 Wire system 

5VA

AUX

V1, V2, V3

 

PT  (optional)

Load 

Line 

V1
V2
V3
VN

5VA

AUX

V1, V2, V3

 

PT  (optional)

V1

V2

V3

VN

RS485

+

+

+

RS485

+

*Note:      Fuse rating 500mA slow blow fuse. 

Load 

Line 

4. WIRING DIAGRAM 

5. MECHANICAL SPECIFICATION

1) Meter display does not turn ON. 

  a) Check that there is power supply applied on AUX supply terminals. 

  b) Check fuse connection (Use fuse connection of specified ratings). 

2) Data displayed / reading incorrect. 

  a) Check that CT/PT ratios are properly set. 

  b) Check if proper configuration mode 

 is correctly set.

Star/Delta/1Phase

  c)  Check if proper frequency selection normal, distortion is selected properly. 

3) PT reading are incorrect / Active Power reading is negative. 

  a) CT connections may be reversed, check and correct CT connection. 

  b) Check Voltage and current phases are connected in proper sequence. 

4) RS485 communication does not work. 
  a) Check baud rate & parity maintained in the connected computers is same as 

meter. 

  b) Memory mapping in software is correct. 
  c) Check d

 of meter is unique & properly maintained. 

evice ID

  d) Check converter is working properly. 

Manufacturer assumes no responsibility for a hazard or damage caused by 
incorrect or non-application of any of the instructions 

 herein. 

mentioned

ELMEASURE shall not be liable for any consequential or resulting injury or 
for  loss,  damage  or  expense directly  or  indirectly  from  the  use  of  this 
product under any circumstance .

s

ELMEASURE does not claim any responsibility for the damage caused by 
using the product directly or indirectly as sufficient care has been taken to 
provide all information regarding the product. The user is advised to use 
according  to  the  operating  instructions,  professional  practices,  wiring 
rules, codes, safety regulations applicable to the given installation.

6. TROUBLE SHOOTING  

7. INFORMATION 

During  normal  operation  of  this  instrument,  hazardous  voltages  are 
present at the rear terminals, which may cause injury or death. Installation, 
disconnection  or  removal  of  the  meter  should  be  carried  out  only  by 
qualified,  trained  personnel,  after  de-energizing  connected  circuit.  The 
warranty will become void incase the seal is broken,  improper installation 
as well as improper grounding. 