Frequency selection
nor (Normal)/dISt (Distortion)
3.5 Enabling and Disabling Auto Scrolling
Press
for 5 Secs. Display shows : Again press
Down
key
down
key to disable. Display shows :
Starting Voltage
(V.SUP)
Starting Current
(A.SUP)
0.02% to 10.00% of FS
10V - 40V
Parameter 1
selection
( )
1
bASC/
/
thd/Vrh.E/Enr.E VAr/EnrG
POWr (Only for 6425,6435,6445)
Parameter 2
selection
( )
2
bASC/
/
thd/Vrh.E/Enr.E VAr/EnrG
POWr (Only for 6425,6435,6445)
Parameter
3
selection
(3)
bASC/
/
thd/Vrh.E/Enr.E VAr/EnrG
POWr (Only for 6435,6445)
Parameter
4
selection
(4)
bASC/
/
thd/Vrh.E/Enr.E VAr/EnrG
POWr (Only for 6445)
Bar graph
A/VA/WAtS
3.6 Entering and Exit for Old Parameter
Press
for 5 Secs. Display shows : Again press
Up
key
up key for
5 Secs to exit.Display shows :
Dimension Bezel:
96 x 96 mm
(Depth 30/ 6mm behind Bezel)
4
Panel Cutout:
90 × 90 mm
+2
-0
+2
-0
41
96
90
90
96
90
+2
-0
90
+2
-0
30
46
96
90
90
96
57
90
+2
-0
90
+2
-0
No of Poles(POLES)
2 - 28 poles
Demand Period
( )
5
1 - 30 (Only for 6400)
Single phase Connection
5VA
AUX
V1, V2, V3
PT (optional)
V1
VN
RS485
+
+
Load
Line
Delta Connection (2E) 3 Phase 3 Wire system
Star Connection (3E) 3 Phase 4 Wire system
5VA
AUX
V1, V2, V3
PT (optional)
Load
Line
V1
V2
V3
VN
5VA
AUX
V1, V2, V3
PT (optional)
V1
V2
V3
VN
RS485
+
+
+
RS485
+
*Note: Fuse rating 500mA slow blow fuse.
Load
Line
4. WIRING DIAGRAM
5. MECHANICAL SPECIFICATION
1) Meter display does not turn ON.
a) Check that there is power supply applied on AUX supply terminals.
b) Check fuse connection (Use fuse connection of specified ratings).
2) Data displayed / reading incorrect.
a) Check that CT/PT ratios are properly set.
b) Check if proper configuration mode
is correctly set.
Star/Delta/1Phase
c) Check if proper frequency selection normal, distortion is selected properly.
3) PT reading are incorrect / Active Power reading is negative.
a) CT connections may be reversed, check and correct CT connection.
b) Check Voltage and current phases are connected in proper sequence.
4) RS485 communication does not work.
a) Check baud rate & parity maintained in the connected computers is same as
meter.
b) Memory mapping in software is correct.
c) Check d
of meter is unique & properly maintained.
evice ID
d) Check converter is working properly.
Manufacturer assumes no responsibility for a hazard or damage caused by
incorrect or non-application of any of the instructions
herein.
mentioned
ELMEASURE shall not be liable for any consequential or resulting injury or
for loss, damage or expense directly or indirectly from the use of this
product under any circumstance .
s
ELMEASURE does not claim any responsibility for the damage caused by
using the product directly or indirectly as sufficient care has been taken to
provide all information regarding the product. The user is advised to use
according to the operating instructions, professional practices, wiring
rules, codes, safety regulations applicable to the given installation.
6. TROUBLE SHOOTING
7. INFORMATION
During normal operation of this instrument, hazardous voltages are
present at the rear terminals, which may cause injury or death. Installation,
disconnection or removal of the meter should be carried out only by
qualified, trained personnel, after de-energizing connected circuit. The
warranty will become void incase the seal is broken, improper installation
as well as improper grounding.
8. CAUTION