background image

 

 

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200609_01F   Jan 2021                      ©2019 ELMDENE INTERNATIONAL LTD  

 
Fault Diagnostic table 

 Internal - Engineer 

Orange LED 

Diagnostic 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery fully charged 

None 

O

FF

 

Standby 

Operation 

Mains Lost. No faults present 
Battery driving load 

Investigate loss of mains 

F

LASH 

C

ONTINUOUS

 

O

N

 or O

FF

 

No output 

Output fuse blown 
Output overload 
Output short circuit 

Check and replace output 
fuse 
Disconnect output load and 
test load 

1

 

P

ULSE

 

O

N

 

Battery 

Charging 

No faults active 
Battery charging normally but  
< 90% of full charge 

None 

2

 

P

ULSES

 

O

N

 

No Battery 

Battery disconnected 
Battery fuse blown 
Battery heavily discharged 

Check battery connections 
Check battery fuse 
Check battery condition 
Replace battery if aged 

O

FF

 

Low Battery 

Volts 

Standby Mode 
Battery almost discharged 

Restore mains 

3

 

P

ULSES

 

O

N

 or O

FF

 

Battery Fault 

High impedance in battery 
connection 
Battery internal fault 

Check battery connections 
for corrosion. Replace 
battery if aged 

4

 

P

ULSES

 

O

N

 or O

FF

 

Charger Fault 

Internal failure of battery charger 

Return to manufacturer 

5

 

P

ULSES

 

O

N

 or O

FF

 

Battery 

Temperature 

Probe Fault 

Battery temperature monitor 
disconnected or damaged 
PSU running in Safe Mode  

Check temperature sensor 
connections and condition 
of sensor. 
Replace if suspect 

 

 

Summary of Contents for STX2405-MOD

Page 1: ...ents premature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss...

Page 2: ...5 0A 5 0 A 5 0A 5 0 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 2 1Ah 12V PS12021 NP2 1 12 2 x 7Ah 12V PS12070 NP7 12 2 x 17Ah 12V PS12170 NP17 12 BS131N Battery Charging C...

Page 3: ...ault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOS...

Page 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Page 5: ...s less than 60V dc Cable Sizing 1 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 3...

Page 6: ...Figure 3 Terminal labels Standby Batteries 10 With mains disconnected connect the two 12V standby batteries in series using the single cable provided Connect the negative of one battery to the positiv...

Page 7: ...contact NOTE Batteries must be connected before mains power is applied to enable the batteries to be utilised When replacing batteries re connect new batteries and then cycle the mains power OPERATING...

Page 8: ...l regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See...

Reviews: