Sagab by Elma 900
10
Appropriate usage
The instrument may only be used under those conditions and for those purposes for which
it was conceived. For this reason, in particular the safety references, the technical data
including environmental conditions and the usage in dry environments, must be followed.
When modifying or changing the instrument, the operational safety is no longer ensured.
The instrument may only be opened by an authorized service technician, e.g. for fuse
replacement.
Specifications
LED voltage range
12, 24, 36, 50, 120, 230, 400V AC/DC
LED resolution
±12, 24, 36, 50, 120, 230, 400V AC/DC
Tolerances
-30% to 0% of reading
Voltage detection
Automatic
Polarity detection
Full range
Range detection
Automatic
Response time
<0.1s LED
ACV frequency range
50/60Hz
Internal basic load
Approx. 10W at 400V
Peak current
1s<0,2A/ (5s <3,5mA)
Operation time
30s
Recovery time
10 min
LED on
About 12V AC/DC
Impedance
≤
450k
Ω
Temperature range
-10°C to +55°C
Humidity
Max 85% relative humidity
Overvoltage class
CATIII 400V
Voltage tester description
1. Instrument test probe [+] (L1)
2. Handle test probe [-] (L2)
3. LED voltage display