6/8
INSTALLATION
Rear view
WARNING
:
In the wires access used M20 Cable/Tube Gland.
Apply the supplied stickers on the four clips for front panel opening and the side hole for wires,
indicated with
“
A
”.
Install on a wall by using the relevant fixing holes placed on the bottom of the enclosure (as
illustrated in the picture).
Connect the device TM24-A according to the schematic illustrated in the picture.
Important: connect the end of line resistor, used for supervising the connection between the control
panel and type “C” fire alarm devices, to the DC OUT terminal block of the final device connected to
the siren line. The value of the end of line resistor is indicated in the documentation of the fire
detection control panel.
How to mount the pictographs into the device:
Remove the cover from the base by acting on the clips;
Remove the transparent part from the cover by acting on the clips;
Insert the desired pictograph between the transparent part and the cover;
Re-assemble the transparent part on the cover and insert the 2 provided rubber blocks, as
illustrated in the picture, on the retention hooks with lower protrusion; close the cover to the base
by observing the alignment arrows
.
Secure the cover with the provided screws.