ELR60RT 2PH/60
12. ALIGNING THE BARRIERS
For correct alignment, once the barriers are installed, point the optics units of the transmitters and those of the
receivers towards each other. Adjust the lens-holder horizontally by moving it manually after loosening the release
screw on the pivot, and vertically via the front screw to the left of the lens.
Note: Tighten the pivot release screw after making the adjustment
CALIBRATION USING THE SMA SYSTEM
The calibration can be improved by using the supplied filter:
1) Fold the device along the provided creases
2) Place the filter in front of the TX optics, positioning the two hooks on the optics fork pins, to fine-tune the
search for the alignment signal in the case of critical conditions.
It is sufficient to use the filter on the TX only, with no need to repeat the operation on the RX.
Vertical positioning
Horizontal positioning
PIVOT RELEASE SCREW