C302
16/24
- If the Fire Door check is active, the Control Panel verifies that the door is latched to the
Electromagnet in case of normal operation, and that it is closed after a time of
approximately 30 seconds in the alarm condition and with the door holders released.
In Alarm condition from Detection Line and with the fire door not closed, and subsequently
in case of short-circuit of the Detection Line, the Control Panel turns off the Green Led and
the external Detection Line, while the Alarm Red Led indication and the lamp are
permanently alight and the Fault Led and the Buzzer operate discontinuously.
Alight
Control Panel Operation (following a beep after 4
seconds )
Green Led
Off
Control Panel with door holders and Detection Line
excluded
Red Led
Permanently alight
Alarm condition
Off
Detection Line Corrected
Flashing
Detection Line not Completed (buzzer sounds in
pulsive way)
Yellow
Led
Alight + Green Led
off
Detection Line Short Circuited (buzzer sounds
continuosly)
0
Control Panel Operating
Switch
1
Control Panel Excluded, Green Led Off
EXTERNAL Detection Line Excluded
The door holders are NOT Powered
The supplies to the field and to the Batteries are
present
3 Dimensions and drilling template