Elko ATS-2D Quick Start Manual Download Page 2

2 / 2

 ATS-2D         ATS-2DR         ATS-2WR

1

 

2

 

3

1

2

3

4

19

20

21 22

24

23

8

x

Warning

Device is constructed for connection in 1-phase main alternating current voltage and must be installed according to norms valid in the state of application. Connection according to the details in 
this direction. Installation, connection, setting and servicing should be installed by qualifi ed electrician staff  only, who has learnt these instruction and functions of the device. This device contains 
protection against overvoltage peaks and disturbancies in supply. For correct function of the protection of this device there must be suitable protections of higher degree (A, B, C) installed in front 
of them. According to standards elimination of disturbancies must be ensured. Before installation the main switch must be in position “OFF” and the device should be de-energized. Don´t install 
the device to sources of excessive electro-magnetic interference. By correct installation ensure ideal air circulation so in case of permanent operation and higher ambient temperature the maximal 
operating temperature of the device is not exceeded. For installation and setting use screw-driver cca 2 mm. The device is fully-electronic - installation should be carried out according to this fact. 
Non-problematic function depends also on the way of transportation, storing and handling. In case of any signs of destruction, deformation, non-function or missing part, don´t install and claim at 
your seller it is possible to dismount the device after its lifetime, recycle, or store in protective dump.

              

Technical parameters

Supply

Supply terminals:

Supply voltage:

Power consumption (max.):

Supply voltage tolerance:

Time circuit

Program:

Number of switching segments:

Minimum switching interval:

Operating accuracy:

Power reserve:

Output

Number of contacts:

Rated current:

Breaking capacity:

Switching voltage:

Mechanical life:

Electrical life (AC1):

Other information

Operating temperature:

Storage temperature:

Dielectric strength:

Operating position:

Mounting:

Protection degree:

Overvoltage category:

Pollution degree:

Max. cable size 

(mm

2

):

Dimensions:

Weight:

Standards:

4,5

AC 230V (50/60 Hz)  

        

1W (1.5 VA)

-10%, +10%

daily                                 daily                        weekly

48

1s/day

                            max. 150h

1x switching (AgNi)

16A/AC1

3500 VA/AC1

250 V AC

1.000.000 operations

50.000 operations

-10 to +50°C (14 to 122°F)

-10 to +50°C (14 to 122°F)

4kV (supply - output)

any

DIN rail EN 60715

IP20

III.

2

max. 1x 4, max. 2x 1.5 /

s dutinkou max. 1x 4, max. 2x 1.5 (AWG 12)

90 x 35 x 60 mm (3.5˝ x 1.4˝ x 2.4˝)

117 g (4.1 oz.)

EN 61812-1, EN 60669-1, EN 63044-1

Setting 

Example:
06:00 ... 12:00 

ON

12:00 ... 14:00 OFF
14:00 ... 19:30 

ON

19:30 ... 06:00 OFF

   = OFF

 = ON

   = OFF

 = ON

Minimum switching interval:

- daily 30 minutes (1 segment)
- weekly 210 minutes (1 segment)

High temperatures can aff ect the accuracy of the time switches

Lower the segments all the way down

ON

OFF

30 min

30 min

3.5 hour

Power reserve (models only ATS-2DR, ATS-2WR)

The time switch starts working approx. 5 minutes after being connected to the 
power supply. After approximately 72 hours from the connection to the power 
supply, the power reserve, reaches it´s complete charge of 150 hours.

1

 =         switches automatically according to the set program

2

 =         

3

 = 

  

  

permanently closes
permanently opens

Operating mode

+

-

Reviews: