Installation Steps
IT IS ESSENTIAL THAT YOU FOLLOW 
CLOSELY STEPS 1 TO 7 OF THE MOUNTING 
AND INSTALLATION INSTRUCTIONS 
BELOW. FAILURE TO DO SO WILL 
INVALIDATE THE WARRANTY.

Step 1 

Please ensure that you position the PIR in 
the correct place by reading the Positioning 
section of these instructions. For flush 
mounting cut a clean hole measuring 
64mm in diameter in the chosen area for 
the sensor. Seal any large holes on ceiling 
to prevent air current activation.

Step 2

Ensure that the mains power to the circuit 
is switched off. Ensure terminal cover 
and cable clamp are correctly fitted with 
screws supplied. Place the Live In into the 
Terminal marked Live In and the switched 
Live Out into the Live Out terminal.  
Place the neutral into the connection 
marked N for neutral. Please note that it is 
essential that the Live In wire and the 
switch Live Out and Neutral are identified 
prior to commencing installation. 
To connect multiple units connect the live 
switch live and neutrals as shown in 
Diagram 2. Turn off mains supply for 
installation as live working is not 
recommended and can damage the unit.

Step 3

For flush mounting fold the two arms up 
into the vertical position and insert unit 
into the hole. Release unit ensuring arms 
are securely in place.

Step 4

Remove the fascia by turning anti-clockwise 
to show the lux pot, time delay pot switches. 
Please adjust the Lux Level and time delay 
potentiometer gently without force as this is 
a sensitive electronic part. After adjustment 
please wait 30 seconds for changes to take 
effect. It is recommend product is set up 
initially on the minimum 30 second time 
setting to enable an efficient walk test to 
check PIR area coverage.

Step 5

To manually set the desired Lux level adjust 
potentiometer between (+) and (–). This allows 
the PIR to only switch ON ambient light 
levels is below the set level. Adjustment to 
the plus (+) will allow the PIR to always 
switch ON when triggered. A minus - setting 
will effectively switch PIR OFF completely.

Step 6

To increase the time delay turn the 
potentiometer toward the High (H) and
to decrease the time delay turn the 
potentiometer toward the Low (L).

Step 7

The PIR will take approximately 1 minute
to initialize and will flash occasionally after 
the mains power is first applied to allow 
the sensor to learn its environment. 
The load will be ON and after initializing 
will then switch off if there is no
detection in the zones.

3

INSTRUCTION GUIDE

 

|

 

FLUSH MOUNT PIR TIMER – 3 WIRE

Summary of Contents for 374C-1

Page 1: ...h off the load after the adjustable time period has elapsed If infra red heat is detected again during the timing period the timing sequence will restart The unit has a lux level adjustment which measures the ambient light levels and prevents lighting being switched on when there is sufficient lighting in the room A power factor correction capacitor of 4 microfarads may be required when switching ...

Page 2: ...or direct sunlight or in areas with high reflective surfaces Diagram 2 Do not site units on a vibrating surface or near forced air heating and ventilation They should not be placed within 1 metre of the load Sensors work when objects move across their field of view Position the sensor where people will be detected walking across the zones rather than towards the zones identified in Diagram 1 2 INS...

Page 3: ...ing fold the two arms up into the vertical position and insert unit into the hole Release unit ensuring arms are securely in place Step 4 Remove the fascia by turning anti clockwise to show the lux pot time delay pot switches Please adjust the Lux Level and time delay potentiometer gently without force as this is a sensitive electronic part After adjustment please wait 30 seconds for changes to ta...

Page 4: ...peration the PIR will now sense infra red heat when a person or source of heat passes through the detection zone Each time the PIR is triggered it will reset the timer back to the start of the timing period The unit will then wait 5 seconds before allowing the PIR to sense and re trigger the timing period again If no one is present in the room or the detection zone is not passed through during its...

Reviews: