Page 14
M1XRF2G Installation Manual
After the first M1XRF2G Receiver has been installed, additional receivers can be installed for redundancy or improved coverage
and range. Each addtional receiver will need its own data bus address and will need to be enrolled into the control. The data
bus address setting of any additional "redundant" Receivers can be any unused data bus address except for addresses 13, 14,
15, 16.
NOTE: While M1XIN Expanders cannot be assigned to addresses overlapped by wireless zones this is not true for M1XRF2G
Receivers. From the example above, addresses 3, 4, and 5 could be used by additional "redundant" Receivers. In theory it
is possible to install up to 11 total M1XRF2G Receivers onto a single M1 or M1EZ8 control, but only if there were NO M1XIN
Expanders installed.
* For large installations or added coverage in areas with poor wireless conditions, additional M1XRF "Redundant" Receivers can be connected to
the data bus. Redundant receivers must be addressed and enrolled for proper supervision. Loss of any enrolled bus device causes a Missing Bus
Device Trouble. NOTE: Redundant M1XRFs can be set to any of the unused addresses that fall in the total wireless zone number assignments.
Offices
Shipping
M1XRF2G
M1XRF2G
M1XRF2G
Warehouse
Production
Sales
EXAMPLE OF LARGE COMMERCIAL BUILDING with 3 M1XRF2G Receivers
Appendix C - Installing Multiple Redundant Receivers