background image

USER INTERFACE

The user has a display and four keys for
controlling status and programming of the
instrument.

KEYS AND MENUS

UP key

Scrolls through the menu 
items 
Increases the values

DOWN key 

Scrolls through the menu items
Decreases the values

fnc key 

ESC function (exit)

set key 

Accesses the setpoint
Accesses the menus
Confirms the commands
Displays the alarms (if active)

At start-up the instrument performs a
Lamp Test; for five (5) seconds the display
and the leds blink, in order to verify their
integrity and correct operation; afterwards
it will appear the label “Lod” (Loading) for
ten (10) seconds. The instrument has two
main menus: the “Machine Status” and
“Programming” menu.

ACCESSING AND USING MENUS

Resources are arranged in a menu, which
can be accessed by pressing and quickly
releasing the “set” key (“Machine Status”
menu) or by holding down the “set” key
for more than 5 seconds (“Programming”
menu).
To access the contents of each folder, indi-
cated by the relevant label, just press the
“set” key once.
You can now scroll through the contents
of each folder, modify it or use its func-
tions. If you do not use the keyboard for
over 15 seconds (time-out) or if you press
the “fnc” key once, the last value shown
on the display is confirmed and you return
to the previous screen mask.

MACHINE STATUS MENU

To access the “Machine Status” menu
Press and quickly release the  “set” key.
The  label “SP1” appears. 
By using the “UP” and “DOWN” keys you
can scroll through the other folders in the
menu:
-AL: alarm folder (if alarms present);
-SP1: Setpoint 1 setting folder.

Setpoint Setting

Access the “Machine Status” menu by
pressing and quickly releasing the “set”
key. The label of the  “SP1” folder appears.
To display the Setpoint value press the
“set” key again.
The value appears on the display.
To change the Setpoint value, use the “UP”
and “DOWN” keys  within 15 seconds.
If the parameter is LOC = y the Setpoint
cannot be changed.

PROGRAMMING MENU

To enter the “Programming” menu, press
the “set” key for more than 5 seconds.
If specified, the access PASSWORD will be
requested, (parameter “PA1”), and the
label of the first folder will follow. 
To scroll through the other folders, use
the “UP” and “DOWN” keys.
To enter the folder, press “set”. The label
of the first visible parameter appears. To
scroll through the other parameters, use
the “UP” and “DOWN” keys; to change the
parameter, press and  release “set”, then
set the desired value using the “UP” and
“DOWN” keys, and confirm with the “set”
key to move to the next parameter.

PLEASE NOTE

: It is strongly recommended

to switch off and switch on again the con-
troller anytime parameters have been
changed to prevent malfunctioning on
configuration and/or ongoing timings.

PASSWORD

The password “PA1” allows access to level
1 parameters. In the standard configura-
tion passwords are not present.
To enable them and assign them the
desired value, access the “Programming”

menu, within the folder with the  “diS”
label. If passwords are enabled, you will
see it at the entrance of the “Program-
ming” menu.

COPY CARD

The Copy Card is an accessory connected
to the TTL serial port which allows pro-
gramming quickly the instrument parame-
ters (upload and download parameter’s
map). The operation is performed as fol-
lows:

Format

This command allows copy card formatting,
an operation necessary in case of first use
or to copy maps with different models.
Warning: if the copy card has been pro-
grammed, using the “Fr” the data entered
are erased. This operation cannot be can-
celled.

Upload

This operation loads the programming
parameters from the instrument.

Download

This operation downloads to the instru-
ment the programming parameters. 
The operations are performed accessing
the folder identified by the “FPr” label and
selecting, according to the case, “UL”, “dL”
or “Fr” commands; the operation is con-
firmed by pressing the “set” key. If the
operation is successful an “y” is displayed,
on the contrary, if it fails a “n” will be dis-
played.

Download “from reset (instrumennt
OFF”

Connect the Copy Card with the instru-
ment OFF (not under voltage).
When the instrument is switched on the
programming parameters will be down-
loaded into the instrument (this operation
takes about 15 seconds); after the lamp-
test  the diplay will show for about 5 sec-
onds:
• label dLY if copy operation successful
• label DLn if not

PLEASE NOTE:

• after the download operation the instru-
ment will immediately work with the new
parameters map setting

KEYBOARD LOCKING

The instrument includes a facility for dis-
abling the keyboard, by programming the
“LOC” parameter (see folder with “diS”
label). If the keyboard is locked, you can
still access the programming menu by
pressing the “set” key.
The Setpoint can also be viewed.

IC 912 Pt100-TC

single stage electronic controller

fnc

set

LED

Position

Related Function 

Status

OUT1

relay 1 (OUT1)

ON when the regulator is started up; blinking in case of delay, 
protection or blocked enabling

Alarm 

ON when the alarm is enabled;

Summary of Contents for IC 912 Pt100-TC

Page 1: ...se set then set the desired value using the UP and DOWN keys and confirm with the set key to move to the next parameter PLEASE NOTE It is strongly recommended to switch off and switch on again the con troller anytime parameters have been changed to prevent malfunctioning on configuration and or ongoing timings PASSWORD The password PA1 allows access to level 1 parameters In the standard configura ...

Page 2: ...ference standards on safety It is classified as follows according to its manufacture as an auto matic electronic control device to be incorporated by independent mounting according to its automatic operating fea tures as a 1 B type operated control type as a Class A device in relation to the cat egory and structure of the software UNPERMITTED USE Any other use other than that permitted is de facto...

Page 3: ...or is always on while at OF1 0 it functions always in duty cycle mode see Duty Cycle Diagram OFF time regulator 1 Regulator in disabled state time in the event of a faulty probe If set to 1 with On1 at 0 the regulator is always off while at On1 0 it functions always in duty cycle mode see Duty Cycle Diagram DISPLAY folder with diS label keyboard LOCk set and keys Keyboard locking However you can e...

Page 4: ...relays with 8 3 1 2 hp 250V capability Wiring diagram SP1 SP1 dF1 dF1 Off On HC1 H ON OFF Regulation Diagram OF1 Off On OUT On1 On1 parameters On1 ed OF1 programmed for the duty cycle When the analogue input detects an error condition the code E1 is displayed the regulator is activated as indicated by the On1 and OF1 parameters if pro grammed for the duty cycle Duty Cycle Diagram On1 0 0 0 0 OF1 0...

Reviews: