background image

IC 912 LX Pt100 °R

8/8

Wiring diagram

WIRING  (12V and 230V supply)

1 - 2

N.O. regulator relay output (OUT1)

1 - 3

N.C. regulator relay output (OUT1)

6 - 7

Power supply 1,5 VA max. (12V version)
Power supply 3 VA max. (230V version)

8 - 9

Digital Input (D.I.)

*10-11-12

Pt100 3 wires input

A

TTL input for Copy Card and Televis

System

PLEASE NOTE: 

• User Default Settings
• for relay capacities check on the instrument label
In the diagram there are shown only 12V and 230V supply
and relays with 8(3) 1/2 hp 250V capability

Pay extreme attention to the probe connection polarity.

IC 912 LX Pt100 - 12 V

A

6 7

10 11 12

1 2 3

8 9

D.I.

Pb1

OUT1

Supply

IC 912 LX Pt100 - 230 V

A

6 7

10 11 12

1 2 3

8 9

D.I.

OUT1

Supply

Pb1

Eliwell & Controlli s.r.l.

Via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Tel39 0437 986111
Fac39 0437 989066
Internet http://www.eliwell.it

Technical Customer Support:

Email: [email protected]
Tel39 0437 986300

Climate Controls Europe
An Invensys Company

11/2004 eng 
cod. 9IS23094

SP1

SP1-dF1

dF1

Off

On

HC1=H

SP1+dF1

SP1

dF1

Off

On

HC1=C

HC1 Heat/Cool Mode. 
SP1 Setpoint 1. 
dF1 diFferential. Relay 1 tripping
differential. 

ON-OFF REGULATION DIAGRAM

RS232 (to PC)

RS485

BusAdapter

PCInterface

TTL

PC with 

Televis package

230V

N

L

230V

N

L

The Televis remote control systems can be connected using the TTL serial port
(the TTL- RS 485 BUS ADAPTER 130 or 150 interface module must be used). 
To configure the instrument to do this, you need to access the folder with the
“Add” label and use the “dEA” and “FAA” parameters.

TELEVIS SYSTEM

BUS

Adapter130/150

TTL - RS-485 serial interface on DIN rail
for connecting device and a RS-485
network designed for connection to
Televis monitoring system.

PC

Interface1100

RS-232/RS-485 serial interface for con-
necting a PC and a series of instru-
ments in an RS-485 network. The
device needs the Blue

Card

activation

module supplied with the Eliwell soft-
ware package licence to be plugged in.

Summary of Contents for IC 912 LX Pt100 R

Page 1: ...probe errors the AL label appears By using the UP and DOWN buttons you can scroll through the other folders in the menu the folders are indicated below in the order they appear SP1 Set point 1 setting folder or AL alarm folder if alarms present with exception of faulty probes probe errors Pb1 probe 1 value folder IC 912 LX Pt100 R electronic controller with single output and regulation in Réaumur ...

Page 2: ...ing parameters to the instrument NOTE UPLOAD instrument Copy Card DOWNLOAD Copy Card instru ment The operations are performed by access ing the folder identified by the FPr label and selecting the UL dL or Fr commands The operation is confirmed by pressing the set button If the oper ation is successful a y is displayed whereas if it is unsuccessful an n will be displayed Download from reset Connec...

Page 3: ...tton and the value 0 will appear enter the password using the UP DOWN buttons and press the set button again This allows you to access the level 2 parameters The first folder that appears is CP NOTE At this level the folders will only display all the level 2 parame ters Therefore level 1 parameters will only be visible if you quit the Programming Menu and repeat proce dure 1 NOTE It is strongly re...

Page 4: ... label on the instrument Buzzer output only on models with Buzzer Measuring range from 150 to 1350 Accuracy 0 5 for all scale 1 digit 0 2 from 120 to 240 C Resolution 0 1 R within 199 9 C 1 R over Consumption model 230V 3 VA max model 12 24V 1 5 VA max Power supply 12 24 Va c 10 or 230Va 10 50 60 Hz Warning check the power supply specified on the instrument label for relay and power supply capacit...

Page 5: ...ART function ALARMS folder with AL label Alarm type Parameter HA1 and LA1 modes as temperature absolute values or as differential compared to the Setpoint 0 absolute value 1 relative value Alarm Fan differential Alarm differential Power on Alarm Override Alarm exclusion time after instrument switch on after a power failure Setpoint Alarm Override Exclusion alarm time until Setpoint is reached 0 di...

Page 6: ...from power on WARNING If set 0 it is not active if set 0 output will not be activated before this time Configuring digital inputs 0 disabled 1 SOFT START 2 Offset Setpoint 3 outputs stopped 4 not used 5 auxiliary output 6 stand by 7 maintenance requested 8 external alarm 9 external alarm stop regulators Polarity and Priority Digital Input no normally open nc normally closed noP normally open with ...

Page 7: ...ulators if speci fied by the H11 9 parameter This alarm condition can be viewed in the AL folder with the label EA The relay can be silenced even if alarm icon starts blinking controls stay locked until the next time the digital input is deactivated DIAGNOSTICS DISPLAY E1 FAULT Faulty probe 1 thermostat control Table of faulty probes DISPLAY AH1 AL1 EA Opd Press any button to silence the alarm The...

Page 8: ...ustomer Support Email techsuppeliwell invensys com Telephone 39 0437 986300 Climate Controls Europe An Invensys Company 11 2004 eng cod 9IS23094 SP1 SP1 dF1 dF1 Off On HC1 H SP1 dF1 SP1 dF1 Off On HC1 C HC1 Heat Cool Mode SP1 Setpoint 1 dF1 diFferential Relay 1 tripping differential ON OFF REGULATION DIAGRAM RS232 to PC RS485 BusAdapter PCInterface TTL PC with Televis package 230V N L 230V N L The...

Reviews: