65
CP09
Enable saturation cut-off
0…1
1
1
1
num
CP10
Activation Policy
0…2
1
1
1
num
CP11
Enable/disable sequence of relays associated to compressor
power stages in the suction section
0…2
2
2
2
num
CP12
Compressor min. OFF-ON time
0…255
1
1
1
min
CP13
Compressor min. ON-ON time
0…255
1
1
1
min
CP14
Compressor min. ON-OFF time
0…255
15
15
15
secs
CP15
Interstep up time
0…255
30
30
30
secs
CP16
Interstep down time
0…255
10
10
10
secs
CP17
Maximum hours of use for compressor
0…6500
0
0
0
Hours*10
CP18
Minimum speed
0…100
20
20
20
%
CP19
Maximum speed
0…100
80
80
80
%
CP20
Saturation speed
0…100
100
100
100
%
CP21
Default power for non-allocated probe/probe error
0…100
0
0
0
%
CP22
Number of compressor steps per circuit
0…4
4
4
4
num
CP23
Number of compressor steps 1
1…4
1
1
1
num
CP24
Number of compressor steps 2
1…3
1
1
1
num
CP25
Number of compressor steps 3
1…2
1
1
1
num
Fn
Folder
Fn00
Regulation setpoint
Fn01…Fn02 151
-
151
CFBP
Fn01
Setpoint bottom limit
-999…Fn02 -500
-
-500
CFBP
Fn02
Setpoint upper limit
Fn01…9999 999
-
999
CFBP
Fn03
Proportional band
0…9999
20
-
20
CFBP
Fn04
Delta minimum cut-off
0…9999
20
-
20
CFBP
Fn05
Delta saturation cut-off
0…9999
20
-
20
CFBP