E-70-Ö DIGITAL CONTROLLER USER MANUAL
5. CONNECTION DIAGRAM
Before operating the controller, ensure that the controller
is correctly configured. Incorrect configuration could
result in damage to the process being controlled.
m
The terminals 01 to 07 are electrically live. While the
instrument is powered, never touch to these terminals.
m
The labels on the sides of the controller identify the ordering
code (Type), serial number and wiring connections.
Connection diagram is given below.
Manufacturer / Technical Support:
Elimko Co. Ltd. 8. cadde 68. Sokak No:16 06510 Emek - ANKARA / TURKEY
Phone:+ 90 312 212 64 50 Fax:+ 90 312 212 41 43 www.elimko.com.tr e-mail:[email protected]
KY-70-1209-0-Ö
The front panel view of the E-70-Ö controller is given in
section. In normal operation, the four digit display displays the process
value and unit. The display of the controller displays between -19 and 99.
Out of this range or while the connection of the sensor is broken the
display will be shown as (
)
1. DESCRIPTION
--
6. OPERATION
The other parameters are configured in configuration mode.
q
In order to access the configuration mode,
and
buttons must be
pressed simultaneously.
C
D
q
Just after this operation,
message is displayed for one second
duration,
is displayed in the display. The security code must be
entered with
and
buttons in order to access the parameters.
COD
0
A
F
q
The entered security code must be correct, otherwise pressing
button will revert to normal operation.
D
q
The factory setting value of security code is “10”. The security code is
defined by
parameter; user can edit this parameter to define a new
security code. If the value of security code is forgotten, pressing
and
buttons simultaneously at least 10 seconds, makes possible to access
the parameters.
PAS
C
D
q
If the entered security code is correct, pressing
key will select the
first parameter.
C
q
While a parameter is selected, the parameter value is edited by
and
buttons.
Pressing
button will select the next parameter.
Pressing
button exist the configuration mode.
F
A
C
D
16
15
18
19
20
PT-100
02
21
17
04
03
01
06
07
3A
250
VAC
3A
250
VAC
05
24 V AC; 50-60Hz
24 V AC; 50-60Hz
RL1
3A
250
VAC
3A
250
VAC
RL2
7. EXPLANATION OF PARAMETERS
21 C
*
ASTL
0 C
*
SETL
2*C
Code ok.
Code wrong
COD
0
SETH
SFT
0*C
10*C
UNT
PAS
10
0
ASTH
10*C
COD
:
Security code is asked with this parameter. It can be
adjusted between -1999 and 9999.
SFT
:
Defines the shift value of the input. It can be adjusted
between -10°C and 10°C. The value of input that seen
on the display is the sum of measured value and
parameter.
SFT
UNT
:
Indicates the measuring unit of the input. It can be
adjusted as 0 (°C) or 1 (°F). If
parameter is changed,
,
,
,
, and
parameters should be
revised. Also the adjustment limits of set points are depend
on this parameter.
UNT
ASTL ASTH SETL SETH
SFT
PAS
:
Define the security code. Parameter can be adjusted
between -1999 and 9999.
ASTL
:
The low value of alarm set point. This parameter is
used for controlling Relay 2.
ASTH
:
The high value of alarm set point. This parameter is
used for controlling Relay 2.
SETL
:
The low value of control set point. This parameter is
used for controlling Relay 1.
SETH
:
The high value of control set point. This parameter is
used for controlling Relay 1.