CONNECTION DIAGRAM
01
85-265 VAC ; 50 - 60Hz / 85-375 VDC
20-60 VAC ; 50 - 60Hz / 20-85 VDC
02
03
04
05
06
07
08
09
10
13
14
11
12
TC
mA
RT
Tx
+24V
RL1
RL2
B
A RS-485
Tx
GND
E-48
mV
E-48 controller should be installed inside a suitable
grounded metal enclosure (panel). This must
prevent the live parts being accessibleto human
hands and metal tools.
E-48 controller does not include a power switch.
Therefore, the power supply to the controller and power outputs
must be wired through the proper fuse or circuit breaker.
To minimize the pick-up of electrical noise, the wiring of low
voltage lines, particularly the sensor input should be routed away
from the high-current power cables. Where it is not possible, use
shielded cables with the shield grounded at both ends.
The cables used for powering the controller and the power
outputs must conform to the standarts IEC 60245 and IEC 60227.
PANEL MOUNTING
Cut a hole in the panel. (See the figure for overall dimensions.)
Remove the mounting bracket and slide the controller into the cutout
from the front of the panel.
Fit the mounting bracket and slide it until the controller is fastened.
DIMENSIONS
44 mm
44 mm
48 mm
48 mm
FRONT PANEL
R1 Led
R2 Led
PR Led
SF Led
Star
Button
Enter
Button
Up/Down
Buttons
Upper
Display
Lower
Display
10 mm
100 mm
44 mm
E-48
PROCESS CONTROLLER
USER MANUAL
E-48 process controllers are equipment having high reading sensivity and
capability, with no moving parts, having infinite life and very low calibration
drift with time and environment conditions. Indicating method is 2x4 digit LED
display. E-48 indicating range is from -1999 to 9999 and is able to connect
mV, mA, thermocouple, resistance thermometer and other sensors and
transmitters. Controllers have high input empedance and protecting and
warning the system against the breakage sensors.
E-48 series universal process controllers are advanced new generation
microcontroller based industrial instruments designed for On/Off and PID
control forms, dimensions of 48x48 mm compatible with IEC/TR 60668
standarts. Universal inputs and outputs of controller can be programmed
easily by the user.
E-48 process controllers can be used in every field of the industry for the
measurement and control of temperature, pressure, level, speed, current,
voltage, resistance and other physical units; as well asin the industry
branches of iron&steel, cement, plastic, chemistry, metallurgy, petrochemical
refineries, ceramic, glass and others.
E-48 controller is designed for panel mounting and
should be used in an industrial environment.
The package of E-48 controller contains;
Controller and mounting bracket
User manual
Guarantee certificate
After opening the package, please check the contents with the
above list. If the delivered product is wrong type, any item is
missing or there are visible defects, contact the vendor from which
you purchased the product.
Before installing and operating the controller, please read the user
manual thoroughly.
The installation and configuration of the controller must only be
performed by a person qualified in instrumentation.
Keep the unit away from flamable gases, that could cause
explotions.
Do not use alcohol or other solvents to clean the controller.
Use a clean cloth soaked in water tightly squeezed to gently
wipe the outer surface of the controller.
This controller complies with the European Low Voltage Directive
2006/95/EC, by the application of safety standard TS EN 61010-1.
(Pollution degree 2)
This controller complies with the EMC Directive 2004/108/EC
by the application of EMC standard TS EN 61326.
The product life of this instrument is 10 years.
TECHNICAL SPECIFICATION
Thermocouple ( TC ) :
B, E, J, K, L, N, R, S, T, U
Resistance Thermometer ( RT ) :
Pt-100
Current :
0-20 mA, 4-20 mA (Linear)
Voltage :
0-50 mV, 0-1 V, 0.2-1 V (Linear)
Relay :
SPST-NO 250V AC, 3A
Current :
0-20
mA, 4-20
mA, 20-0
mA, 20-4
mA (Isolated)
Pulse :
24V DC, 25 mA (for SSR) (Not Isolated)
Relay :
SPST-NO 250V AC, 3A
2 x 4 digit 7 mm 7 segment led display
o
Thermocouple
:
(±0.5% of the reading value or ±1 C)
±1 digit max.
o
Pt-100
:
(±0.5% of the reading value or ±1 C)
±1 digit max.
Analog Input:
±0.5% FS ±1 digit max.
16 bit
12 bit
On/Off, PID
85-265 V AC / 85-375 V DC
20-60 V AC / 20-85 V DC
4W (7 VA)
o
o
o
o
-10 C, +55 C (+14 F, +131 F)
(with no condensation or icing)
o
o
o
o
-25 C, +65 C (-13 F, +149 F)
(
with no condensation or icing)
10.000.000 operations
(The relay life differs according to the usage
configuration. When the relays are old, their contacts
could melt or burn out.
)
>1.000.000 operations (under 1/10 of load)
EEPROM (100.000 max. write-erase)
155 g
IP 66 Front Panel (NEMA 4X)
IP 20 Rear Case
Protection Class
Input Types
Control Output
Alarm Outputs
Display Type
Accuracy
Analog Digital Converter
Digital Analog Converter
Control Type
Operating Voltage
Power Consumption
Operating Temperature
Storage Temperature
Relay Mechanical Life
Memory
Weight
Relay Electrical Life
TYPE CODING
0:
No Relay
1 Relay
1:
2 Relays
2:
1 Pulse for SSR
3:
1 Relay,1 Pulse for SSR
4:
E-48-W-X-Y-Z
0:
None
RS 485 (If X=0)
1:
0:
85-265 V AC/85-375 V DC
20-60 V AC/20-85 V DC
1:
0:
No Output
1 Analog Output (If Y=0)
1:
The labels on the sides of the controller identify the ordering code
(Type), serial number and wiring connections.
The controller options are also indicated on the wiring diagram.
Before operating the controller, ensure that the
controller is correctly configured. Incorrect
configuration could result in damage to the
process being controlled.
The terminals 01 to 05 are electrically live. While the
instrument is powered, never touch to these terminals.
35 mm min.
+0.2
-0.0
45 x 45 mm
10 mm min.
Panel Cutout and Minimum Spacing
R1 Led
When lit, it indicates that RL1 output is active.
R2 Led
When lit, it indicates that RL2 output is active.
PR Led
When lit, it indicates that the controller is in the
configuration mode.
SF Led
- When lit, it indicates that the controller is in manual mode.
- SF led will also flash when the auto-tuning is in progress.
Star
Button
- When pressed together with
button, password is asked
for entering the configuration page.
- While in configuration pages, pressing this button reverts
to normal operation.
- While in normal operation, pressing this button for duration
3 seconds, toggles between automatic and manual mode.
This operation is disabled if the
MPL
parameter in page
PRTC
is set to
DSB
or if the
CNTL
parameter in
OCNF
page is
set other than
PID
.
- While in normal operation, pressing this button
acknowledges the latched alarms if configured (
A
X
LT
=
ON
).
Enter
Button
- When pressed together with
button, password is asked
for entering the configuration page.
- While in configuration pages, pressing this button selects
the next parameter.
- While in configuration pages, pressing this button for
duration 2 seconds, returns to the top of the page.
- While in normal operation, pressing this button selects the
next parameter in operator page.
Lower
Display
-
While in normal operation, it displays the control set point
(Automatic mode) or manual output (Manual mode).
-
While in configuration pages, it displays the parameter
value.
Upper
Display
- While in normal operation, it displays the process value or
error message.
- While in configuration pages, it displays the name of the
parameters.
Up/Down
Buttons
- While in normal operation, these buttons can be used to
edit the control set point (Automatic mode) or manual output
(Manual mode).
- While in configuration, these buttons can be used to select
the configuration pages and to edit the parameters.
ALARM TYPES
EXPLANATIONS
A1SP
or
a2sp
> 0
LO
HI
LOD
HID
LOB
HIB
OFF
1
ASP
PV
Alarm State
0
0
A1SP
or
a2sp
<
0
A1tp
or
A2tp
Alarm State
PV
0
1
0
Alarm State
Alarm State
PV
0
1
0
ASP
ASP
1
0
0
PV
ASP
Alarm State
1
0
0
SP
SP+ASP
Alarm State
Alarm State
Alarm State
Alarm State
AlarmState
Alarm State
Alarm State
PV
PV
PV
PV
PV
PV
PV
1
0
0
SP
SP+ASP
1
0
0
SP
SP+ASP
0
SP
1
0
1
0
0
SP-ASP
SP
SP+ASP
1
0
0
SP
1
0
0 SP-ASP
SP
SP+ASP
1
0
0
SP
SP+ASP
A
X
HY
Alarm State
PV
1
0
0
Low
Alarm
(Absolute)
High
Alarm
(Absolute)
Low
Deviation
(Relative)
High
Deviation
(Relative)
Band
Alarm
(In)
Band
Alarm
(Out)
Alarm function is cancelled when
A1tp
or
A2TP
parameters are
off
.
Shaded areas
show the
hysteresis.
When alarm state is
"1" the output (relay)
is active.
ERROR MESSAGES
Open
Ufl
Ofl
Nnnn
Vvvv
Message
Meaning
Remedy
The connection of the sensor
is broken.
The process value is below
the sensor type-temperature
interval.
The process value is above
the sensor type-temperature
interval.
The process value is
above the value that can
be displayed.
The process value is
below the value that can
be displayed.
Check the sensor and
the sensor connection.
Check the sensor and
the input type specified
by the
INPT
parameter.
Check the analog value
on the input terminal
and the scalar specified
by the
Dp
,
Zero
and
span
parameters.
INPUT TYPES and RANGES
LINEAR INPUTS
Range
0-20 mA DC
Type
0-50 mV DC
0-1 V DC
0.2-1 V DC
4-20 mA DC
0a20
Current
0v50
Voltage
00v1
Voltage
02v1
Voltage
Current
4a20
Standart
o
( C)
o
( F)
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60751
Type B
Type E
Type J
Type K
Type L
Type N
Type R
Type S
Type T
Type U
Pt-100
B
E
J
K
L
N
R
S
T
U
Pt
60 , 1820
-200 , 840
-200 , 1120
-200 , 1360
-200 , 900
-200 , 1300
-40 , 1760
-40 , 1760
-200 , 400
-200 , 600
-200 , 840
140
3308
-328
1544
-328
1562
-328
2480
-328
1652
-328
2372
104
3200
-328
752
-328
1112
-328
1544
104
,
,
,
,
,
,
,
,
,
,
, 3200
Sensor Type
Temperature Range
TEMPERATURE SENSORS
AUTO-TUNE
Auto-tuning matches the characteristics of the controller to the
process being controlled in order to obtain good control. Tuning
involves calculating and setting the values of the PID parameters.
The Auto-tuner works by switching the output on and off to induce an
oscillation in the process value. From the amplitude and period of
oscillations PID parameters are calculated.
Auto-tune can be performed at any time, but normally it is performed
only once during the initial commissioning of the process. However,
if the process under control subsequently becomes unstable
(because its characteristics have changed), you can re-tune again
for the new conditions.
In order to start Auto-tune process:
1- Set the
CNTL
parameter in
OCNF
page as
PID
.
2- Set the control set point to the value at which you will normally
operate the process. Consider also the process value may exceed
the control set point while in Auto-tuning.
3- Set the
HYS
parameter in
TUNE
page as
0.1
(if
DP
=1) or
1
(if
DP
=0).
4- Set the
AT
parameter in
TUNE
page as
ON
to commence
Auto-tuning process. Press
button to revert the normal operation.
The lower display and SF led will flash to indicate that tuning is in
progress.
After a few cycles of oscillation the tuning is completed and the
calculated PID parameters
PB
,
IT
and
DT
are stored.
While the Auto-tuning in progress if
AT
parameter is set the
OFF
or
operating power of the controller is interrupted Auto-tune progress is
stopped and old PID values are retained.
48