CONNECTION DIAGRAM

01

85-265 VAC ; 50 - 60Hz   / 85-375 VDC

20-60 VAC ;  50 - 60Hz     / 20-85 VDC

02

03

04

05

06

07

08

09

10

13

14

11

12

TC

mA

RT

Tx

+24V

RL1

RL2

B

A RS-485

Tx

GND

E-48

mV

E-48 controller should be installed inside a suitable
grounded metal enclosure (panel). This must
prevent the live parts being accessibleto human
hands and metal tools.

E-48 controller does not include a power switch.
Therefore, the power supply to the controller and power outputs
must be wired through the proper fuse or circuit breaker.

To minimize the pick-up of electrical noise, the wiring of low
voltage lines, particularly the sensor input should be routed away
from the high-current power cables. Where it is not possible, use
shielded cables with the shield grounded at both ends.

The cables used for powering the controller and the power
outputs must conform to the standarts IEC 60245 and IEC 60227.

PANEL MOUNTING

Cut a hole in the panel. (See the figure for overall dimensions.)

Remove the mounting bracket and slide the controller into the cutout
from the front of the panel.

Fit the mounting bracket and slide it until the controller is fastened.

DIMENSIONS

44 mm

44 mm

48 mm

48 mm

FRONT PANEL

R1 Led

R2 Led

PR Led

SF Led

Star

Button

Enter

Button

Up/Down

Buttons

Upper

Display

Lower

Display

10 mm

100 mm

44 mm

E-48

PROCESS CONTROLLER

USER MANUAL

E-48 process controllers are equipment having high reading sensivity and
capability, with no moving parts, having infinite life and very low calibration
drift with time and environment conditions. Indicating method is 2x4 digit LED
display. E-48 indicating range is from -1999 to 9999 and is able to connect
mV, mA, thermocouple, resistance thermometer and other sensors and
transmitters. Controllers have high input empedance and protecting and
warning the system against the breakage sensors.

E-48 series universal process controllers are advanced new generation
microcontroller based industrial instruments designed for On/Off and PID
control forms, dimensions of 48x48 mm compatible with IEC/TR 60668
standarts. Universal inputs and outputs of controller can be programmed
easily by the user.

E-48 process controllers can be used in every field of the industry for the
measurement and control of temperature, pressure, level, speed, current,
voltage, resistance and other physical units; as well asin the industry
branches of iron&steel, cement, plastic, chemistry, metallurgy, petrochemical
refineries, ceramic, glass and others.

E-48 controller is designed for panel mounting and
should be used in an industrial environment.

The package of E-48 controller contains;
Controller and mounting bracket
User manual
Guarantee certificate

After opening the package, please check the contents with the
above list. If the delivered product is wrong type, any item is
missing or there are visible defects, contact the vendor from which
you purchased the product.

Before installing and operating the controller, please read the user
manual thoroughly.

The installation and configuration of the controller must only be
performed by a person qualified in instrumentation.

Keep the unit away from flamable gases, that could cause
explotions.

Do not use alcohol or other solvents to clean the controller.
Use a clean cloth soaked in water tightly squeezed to gently
wipe the outer surface of the controller.

This controller complies with the European Low Voltage Directive
2006/95/EC, by the application of safety standard TS EN 61010-1.
(Pollution degree 2)

This controller complies with the EMC Directive 2004/108/EC
by the application of EMC standard TS EN 61326.

The product life of this instrument is 10 years.

TECHNICAL SPECIFICATION

Thermocouple ( TC ) :

 B, E, J, K, L, N, R, S, T, U

Resistance Thermometer ( RT ) :

 Pt-100

Current :

 0-20 mA, 4-20 mA (Linear)

Voltage : 

0-50 mV, 0-1 V, 0.2-1 V (Linear)

Relay : 

SPST-NO 250V AC, 3A 

Current : 

0-20

 

mA, 4-20

 

mA, 20-0

 

mA, 20-4

 

mA (Isolated)

Pulse : 

24V DC, 25 mA (for SSR) (Not Isolated)

Relay : 

SPST-NO 250V AC, 3A

2 x 4 digit 7 mm 7 segment led display

o

Thermocouple

 

:

 (±0.5% of the reading value or ±1  C)

±1 digit max.

o

Pt-100

 

:

 (±0.5% of the reading value or ±1  C)

±1 digit max.

Analog Input:

 ±0.5% FS ±1 digit max.

16 bit

12 bit
On/Off, PID
85-265 V AC / 85-375 V DC
20-60 V AC / 20-85 V DC
4W  (7 VA)

o

o

o

o

-10  C, +55  C (+14  F, +131  F)
(with no condensation or icing)

o

o

o

o

-25  C, +65  C (-13  F, +149  F)
(

with no condensation or icing)

10.000.000 operations
(The relay life differs according to the usage
configuration. When the relays are old, their contacts
could melt or burn out.

)

>1.000.000 operations (under 1/10 of load)
EEPROM (100.000 max. write-erase)
155 g

IP 66 Front Panel (NEMA 4X)
IP 20 Rear Case

Protection Class

Input Types

Control Output

Alarm Outputs
Display Type

Accuracy

Analog Digital Converter

Digital Analog Converter

Control Type

Operating Voltage

Power Consumption

Operating Temperature

Storage Temperature

Relay Mechanical Life

Memory
Weight

Relay Electrical Life

TYPE CODING

0:

No Relay
1 Relay

1:

2 Relays

2:

1 Pulse for SSR

3:

1 Relay,1 Pulse for SSR

4:

E-48-W-X-Y-Z

0:

None
RS 485 (If X=0)

1:

0:

85-265 V AC/85-375 V DC
20-60 V AC/20-85 V DC

1:

0:

No Output
1 Analog Output (If Y=0)

1:

The labels on the sides of the controller identify the ordering code
(Type), serial number and wiring connections.
The controller options are also indicated on the wiring diagram.

Before operating the controller, ensure that the
controller is correctly configured. Incorrect
configuration could result in damage to the
process being controlled.

The terminals 01 to 05 are electrically live. While the
instrument is powered, never touch to these terminals.

35 mm min.

+0.2

-0.0

45 x 45 mm 

10 mm min.

Panel Cutout and Minimum Spacing

R1 Led

When lit, it indicates that RL1 output is active.

R2 Led

When lit, it indicates that RL2 output is active. 

PR Led

When lit, it indicates that the controller is in the
configuration mode.

SF Led

- When lit, it indicates that the controller is in manual mode.
- SF led will also flash when the auto-tuning is in progress.

Star
Button

- When pressed together with 

 button, password is asked

for entering the configuration page.
- While in configuration pages, pressing this button reverts
to normal operation.
- While in normal operation, pressing this button for duration
3 seconds, toggles between automatic and manual mode.
This operation is disabled if the 

MPL

 parameter in page

PRTC

 is set to 

DSB

 or if the 

CNTL

 parameter in 

OCNF

 page is

set other than 

PID

.

- While in normal operation, pressing this button
acknowledges the latched alarms if configured (

A

X

LT

 = 

ON

).

Enter
Button

- When pressed together with 

 button, password is asked

for entering the configuration page.
- While in configuration pages, pressing this button selects
the next parameter.
- While in configuration pages, pressing this button for
duration 2 seconds, returns to the top of the page.
- While in normal operation, pressing this button selects the
next parameter in operator page.

Lower
Display

While in normal operation, it displays the control set point

(Automatic mode) or manual output (Manual mode).

While in configuration pages, it displays the parameter

value.

Upper
Display

- While in normal operation, it displays the process value or
error message.
- While in configuration pages, it displays the name of the
parameters.


Up/Down
Buttons

- While in normal operation, these buttons can be used to
edit the control set point (Automatic mode) or manual output
(Manual mode).
- While in configuration, these buttons can be used to select
the configuration pages and to edit the parameters.

ALARM TYPES

EXPLANATIONS

A1SP

 or 

a2sp

 

> 0

LO

HI

LOD

HID

LOB

HIB

OFF

 

1

ASP

PV

Alarm State

0

0

A1SP

 or 

a2sp

 <

 0

A1tp

or

A2tp

Alarm State

PV

0

1

0

Alarm State

Alarm State

PV

0

1

0

ASP

ASP

1

0

0

PV

ASP

Alarm State

1

0

0

SP

SP+ASP

Alarm State

Alarm State

Alarm State

Alarm State

AlarmState

Alarm State

Alarm State

PV

PV

PV

PV

PV

PV

PV

1

0

0

SP

SP+ASP

1

0

0

SP

SP+ASP

0

SP

1

0

1

0

0

SP-ASP

SP

SP+ASP

1

0

0

SP

1

0

0 SP-ASP

SP

SP+ASP

1

0

0

SP

SP+ASP

A

X

HY

Alarm State

PV

1

0

0

Low

Alarm

(Absolute)

High

Alarm

(Absolute)

Low

Deviation

(Relative)

High

Deviation

(Relative)

Band

Alarm

(In)

Band

Alarm

(Out)

Alarm function is cancelled when 

A1tp

 or 

A2TP

 parameters are 

off

.

Shaded areas
show the
hysteresis.

When alarm state is
"1" the output (relay)
is active.

ERROR MESSAGES

Open

Ufl

Ofl

Nnnn

Vvvv

Message

Meaning

Remedy

The connection of the sensor
is broken.

The process value is below
the sensor type-temperature
interval.

The process value is above
the sensor type-temperature
interval.

The process value is
above the value that can
be displayed.

The process value is
below the value that can
be displayed.

Check the sensor and
the sensor connection.

Check the sensor and
the input type specified
by the 

INPT

 parameter.

Check the analog value
on the input terminal
and the scalar specified
by the 

Dp

Zero

 and 

span

parameters.

INPUT TYPES and RANGES

LINEAR INPUTS

Range

0-20 mA DC

Type

0-50 mV DC

0-1 V DC

0.2-1 V DC

4-20 mA DC

0a20

Current

0v50

Voltage

00v1

Voltage

02v1

Voltage

Current

4a20

Standart

o

( C)

o

( F)

IEC 60584-1

IEC 60584-1

IEC 60584-1

IEC 60584-1

DIN 43710

IEC 60584-1

IEC 60584-1

IEC 60584-1

IEC 60584-1

DIN 43710

IEC 60751

Type B

Type E

Type J

Type K

Type L

Type N

Type R

Type S

Type T

Type U

Pt-100

B

E

J

K

L

N

R

S

T

U

Pt

60 , 1820

-200 , 840

-200 , 1120

-200 , 1360

-200 , 900

-200 , 1300

-40 , 1760

-40 , 1760

-200 , 400

-200 , 600

-200 , 840

140

3308

-328

1544

-328

1562

-328

2480

-328

1652

-328

2372

104

3200

-328

752

-328

1112

-328

1544

104

,

,

,

,

,

,

,

,

,

,

, 3200

Sensor Type

Temperature Range

TEMPERATURE SENSORS

AUTO-TUNE

Auto-tuning matches the characteristics of the controller to the
process being controlled in order to obtain good control. Tuning
involves calculating and setting the values of the PID parameters.
The Auto-tuner works by switching the output on and off to induce an
oscillation in the process value. From the amplitude and period of
oscillations PID parameters are calculated.

Auto-tune can be performed at any time, but normally it is performed
only once during the initial commissioning of the process. However,
if the process under control subsequently becomes unstable
(because its characteristics have changed), you can re-tune again
for the new conditions.

In order to start Auto-tune process:
1- Set the 

CNTL

 parameter in 

OCNF

 page as 

PID

.

2- Set the control set point to the value at which you will normally
operate the process. Consider also the process value may exceed
the control set point while in Auto-tuning.
3- Set the 

HYS

 parameter in 

TUNE

 page as 

0.1

 (if 

DP

=1) or 

1

 (if 

DP

=0).

4- Set the 

AT

 parameter in 

TUNE

 page as 

ON

 to commence

Auto-tuning process. Press 

 button to revert the normal operation.

The lower display and SF led will flash to indicate that tuning is in
progress.

After a few cycles of oscillation the tuning is completed and the
calculated PID parameters 

PB

IT

 and 

DT

 are stored.

While the Auto-tuning in progress if 

AT

 parameter is set the 

OFF

 or

operating power of the controller is interrupted Auto-tune progress is
stopped and old PID values are retained.

48