Installation and First Start-Up
- 12 -
5.2
Installing of the Sensor Head
5.2.1
Installing Tolerances
Note!
Distance between magnetic ring and active sensor area of the measuring system is between
0.50 mm and 1.00 mm without protection ring, and max. 0.45 mm with protection ring.
Observe the given tolerances when installing the system! Outside this area, proper function-
ing of the device cannot be guaranteed!
Install sensor with M3 screws, see Chapter “Dimensions of Sensor and Magnetic ring”
Table 1 Installing Tolerances
Tolerances
Ride height Sensor/Magnetic Ring
0.5 mm ... max. 1.0 mm without protection ring,
resp. max. 0.45 mm with protection ring
Roll/Pitch
The max. distance of 1 mm must not be exceeded
With protection ring the max. distance of 0.45 mm must not be exceeded
Lateral offset
+/- 1 mm
Figure 5: Installation tolerances of the sensor
5.2.2
Mounting direction of EMAX-RO Sensor to Magnetic Ring
Sensor and magnetic ring have to be mounted to the same direction (direction of arrow). The direction arrows
indicate the positive direction.
Abstand Sensor / Magnetring
Versatz
Kippwinkel
Rollwinkel
Pitch
Ride height /
Magnetic Ring
Lateral offset
Roll