5
Installation and Commissioning
60
If remote communication with the corrector via a cable line (RS485 interface, Ethernet, etc.)
is used it is advisable to use overvoltage protection also for this connection.
As an integral part of overvoltage protection, a protective connection must be made in the
control station (generally at the installation site), which is connected to the main protective
terminal block, to which the PE protective conductor of the supply cable and the grounding of
the building (and possibly other conductive technical wiring are connected) inside the
building - gas, water, heating, air conditioning, etc.).
Note – ELCORplus for Zone 2
If the device is powered from the S4N-PWR3 module, it is powered directly from 230Vac. In
this case, SPD type 3 in a design designed for mains sockets can be used or a mains socket
with an integrated SPD type 3 can be used.
5.5.2.2 Grounding and bonding
The inlet and outlet of the gas pipe to/from the control station must be galvanically separated
from the pipe located inside the control station in order to prevent the flow of balancing
currents through the pipes, which can be a source of interference.
Insulated pipe inside the control station must be perfectly grounded and its individual
components including the gas meter must be perfectly concatenated. In between the
individual parts have not arisen voltage potential which would cause flow disturbance
compensating currents (Fig. 18).
Fig. 18 interconnection pipelines
5.5.2.3 Device grounding
The device (corrector ELCOR, ELCORplus, ELCORplus corrector for zone 2 and the
DATCOM, DATCOMplus, DATCOMplus recorder for Zone 2) does not have to be grounded
from a functional point of view.
In the case of a device with an internal pressure sensor, the device is grounded (connected
to the pipeline) via a pressure sensor housing and a Ø 6mm gas supply pipe from the
pipeline (so-called impulse tube) screwed to it – see Fig. 19.
NOTICE
If the main supply is the absence of surge protectors or their incorrect
connection, the manufacturer of the corrector/recorder cannot guarantee its
correct function.
Summary of Contents for DATCOM
Page 38: ...3 Technical Parameters 36 ...
Page 50: ...5 Installation and Commissioning 48 Fig 7 Examples of data plates ...
Page 83: ...5 Installation and Commissioning 81 Fig 37 Communication via RS232 RS485 using B RS module ...
Page 115: ...7 Technical Description of the Device 113 Fig 57 Functional diagram of ELCOR ...
Page 116: ...7 Technical Description of the Device 114 Fig 58 Functional diagram of ELCORplus ...
Page 122: ...7 Technical Description of the Device 120 Fig 61 Modem replacement ...
Page 159: ...10 Communication with the Device 157 packet ...
Page 174: ...12 Accessories 172 Fig 78 ELCORplus example of use of external modules ...
Page 213: ...Appendix 3 Compass Data Export 211 Preview of generated document ...
Page 215: ...Appendix 3 Compass Data Export 213 3 Export to XLS 4 Export to TXT DOC ...
Page 216: ...Appendix 3 Compass Data Export 214 ...
Page 217: ...Appendix 3 Compass Data Export 215 5 Export of graph ...