Appendix
2: ELCORplus version for Zone 2
203
Fig. 83 The deployment of the cable gland
des.
cable
Type of signal
gland
1
pressure (1. channel)
intrinsically safe
PG7
2
temperature (1. channel)
intrinsically safe
PG7
3
gas meter (1. channel)
intrinsically safe
PG7
4
gas meter HF, encoder
intrinsically safe
PG7
5
gas meter (2. channel), digital inputs (DIN)
intrinsically safe
PG7
6
temperature (2. channel)
intrinsically safe
PG7
7
communication
intrinsically safe
PG7
8
external pressure (2. channel)
intrinsically safe
PG7
9
external power supply (for device and
modem)
standard
PG9
10
digital outputs (DOUT), communication,
event. analog input/output
standard
PG9
Table 38 Cable glands - recommended use for ELCORplus for Zone2
8.3 External power connection
The instrument must have the S4N-PWR3 or S4N-PWR4 module in the SLOT4 position,
depending on the type and size of the supply voltage. The device is delivered with a fitted power
supply module according to the customer's requirements and without a power supply.
NOTICE
In the case of a corrector powered from the 230 V mains, there is a risk of
death if the conductive parts are touched!
For this reason:
Work on the electrical components of the device and connection of the
mains supply of the device must be carried out by a worker with the
Summary of Contents for DATCOM
Page 38: ...3 Technical Parameters 36 ...
Page 50: ...5 Installation and Commissioning 48 Fig 7 Examples of data plates ...
Page 83: ...5 Installation and Commissioning 81 Fig 37 Communication via RS232 RS485 using B RS module ...
Page 115: ...7 Technical Description of the Device 113 Fig 57 Functional diagram of ELCOR ...
Page 116: ...7 Technical Description of the Device 114 Fig 58 Functional diagram of ELCORplus ...
Page 122: ...7 Technical Description of the Device 120 Fig 61 Modem replacement ...
Page 159: ...10 Communication with the Device 157 packet ...
Page 174: ...12 Accessories 172 Fig 78 ELCORplus example of use of external modules ...
Page 213: ...Appendix 3 Compass Data Export 211 Preview of generated document ...
Page 215: ...Appendix 3 Compass Data Export 213 3 Export to XLS 4 Export to TXT DOC ...
Page 216: ...Appendix 3 Compass Data Export 214 ...
Page 217: ...Appendix 3 Compass Data Export 215 5 Export of graph ...