Connecting Inputs
151
The corrector is connected with the encoder by a shielded two-wire cable. The electrical
connection of the encoders with the device is described in Section 5.6.2.5. When making the
connection, the signal polarity must be respected.
The encoder data is transmitted to the corrector in the measurement frequency. Setting a short
measurement frequency shortens the battery life. Section 7.5.1 shows the battery life when using
encoders.
The period of reading the data from the gas meter encoder connected to the instrument by means
of an add-on module located in the SLOT 0 position is limited according to the type of encoder
and the type of module used:
encoder type
module (SLOT 0)
reading period
SCR+
S0-SCR
10 s ÷ 1 hour
NAMUR
S0-NAM
1 min ÷ 1 hour
S0-EXT1, S0-EXT1/HF
10 s ÷ 1 hour
Table 27 Encoders – limitation of reading period
9.4.1 Device Specifics when using the Encoders
When the encoder is connected, the data communication with the corrector takes place on a two-
wire cable. In addition to transferring the absolute value of the gas meter counter reading,
additional information from the meter can be transmitted (serial number, gas meter constant,
number of nines to reverse the counters, etc.). This additional information is downloaded by the
control firmware of
the corrector and used to parameterize the device.
If there is a communication error between the corrector and the encoder, then:
The "*" flag (asterisk) shows on the display of the corrector at the actual primary volume
value.
If the communication error lasts for more than 10 minutes, the volume difference is added to
the counter after the communication has been restored.
The manual setting of the primary volume
V
m
value is blocked for inputs connected to an encoder.
9.4.2 Gas Meter Installing and Replacing
When the gas meter is connected to the corrector, the current reading of the meter is transferred
to the corrector, i.e. the state Vm may change abruptly. In order that this abrupt change is not
falsely reflected in the converted volume Vb (Vbs), the following procedure should be followed:
In the utility SW [42], [43] running on the PC, display the device parameters, select the "SCR
Encoder" object and press the "Encoder Replacement" button. During the exchange of the
encoder, the processing of volume from the meter will be stopped. (You also need to follow
the instructions displayed on the PC screen).
Connect the encoder physically to the corrector.
After connecting the encoder, complete the installation/replacement with the OK button.
During the installation/replacement (i.e. from point 1), no increments are added to the related
counters, and the corresponding counter is marked with an exclamation mark on the display. If
point 3 of this procedure is not performed within one hour of the start of the replacement, the
replacement mode will automatically be terminated in the utility program.
Summary of Contents for DATCOM
Page 38: ...3 Technical Parameters 36 ...
Page 50: ...5 Installation and Commissioning 48 Fig 7 Examples of data plates ...
Page 83: ...5 Installation and Commissioning 81 Fig 37 Communication via RS232 RS485 using B RS module ...
Page 115: ...7 Technical Description of the Device 113 Fig 57 Functional diagram of ELCOR ...
Page 116: ...7 Technical Description of the Device 114 Fig 58 Functional diagram of ELCORplus ...
Page 122: ...7 Technical Description of the Device 120 Fig 61 Modem replacement ...
Page 159: ...10 Communication with the Device 157 packet ...
Page 174: ...12 Accessories 172 Fig 78 ELCORplus example of use of external modules ...
Page 213: ...Appendix 3 Compass Data Export 211 Preview of generated document ...
Page 215: ...Appendix 3 Compass Data Export 213 3 Export to XLS 4 Export to TXT DOC ...
Page 216: ...Appendix 3 Compass Data Export 214 ...
Page 217: ...Appendix 3 Compass Data Export 215 5 Export of graph ...