Always avoid working on live parts of an installation.
Attention
A double isolated connection box may only be replaced by a
double isolated connection box. The double isolated
connection box cannot be replaced by a regular connection box
with automatic earthing.
Functional Description
The 5L4211 connection box is intended to be fitted with one
D0I fuse. The fuse capacity is limited to max 6A.
The phase to be connected to the fuse has to be chosen by the
black selection pin (screw type).
The connection
box is equipped with a ‘Surge protection
device’ (SPD) module.
Assembly
Attention
Remove the fuse during assembly of the connection boxes
1.
Ensure a safe working area during assembly, maintenance
and inspection of the connection box. Disconnect the power
of the primary circuit and make sure it cannot be enabled
unintentionally.
2.
Remove the transparent lid, fuse, selection pin and the
intermediate cover.
3.
Mount the connection box with the upper and lower
connection in the lighting pole.
4.
Remove the cover with SPD (pull off the mantle terminals).
There is a possibility to hook this on top of the connection
box.
5.
Connect the incoming and (if present) outgoing ground
cable to terminals N, 1, 2, 3.
6.
Replace the cover with SPD on the mantle terminals.
7.
For in-line connection of the SPD:
connect the outgoing
cable to the armature to terminals 6 and 7 (spring
connection)
For parallel connection of the SPD:
connect the outgoing
cable to the armature to terminals 4 and 5 (screw
connection)
8.
Tightly mount strain relief block.
9.
Check if the connections are mounted properly and firmly.
10.
Mount the intermediate cover and the selection pin.
11.
Install the fuse. Note: fuse type: D01 (E14), max 6A.
12.
Mount the transparent lid and screw tightly.
Incoming
Outgoing (SPD in-line)
N = Neutral
6 = Neutral wire to armature
1 = Phase L1
7 = Phase wire to armature
2 = Phase L2
3 = Phase L3
Outgoing (SPD parallel)
4 = Neutral wire to armature
5 = Phase wire to armature
If required, incoming terminals N, 1, 2 3 can also be looped to
the next lighting pole.
Attention
Terminal box is provided with phase selection: the phase to be
connected to the fuse has to be chosen by the black selection
pin (screw type).
Wiring Diagram
Maintenance and inspection
The connection box should be situated on a dry and clean
location.
The connection box should be mounted firmly.
The connections should be mounted firmly.
Indicator on SPD is on when power is switched on.
Attention
Always avoid working on live parts of an installation.
Disassembly instruction
1.
Disconnect the power of the main circuit and make sure it
cannot be enabled unintentionally.
2.
Unmount the transparent lid.
3.
Remove the fuse, selection pin and the intermediate cover
4.
Remove the strain relief block.
5.
Disconnect the armature cables.
6.
Remove the SPD
7.
Disconnect the ground cables
8.
Disconnect the connection box from the lighting pole.
Recycling
When the product has reached ‘end of life’, it must be recycled.
Do not dispose this product as unsorted municipal waste.
Contact a qualified recycler for disposal.
Always avoid working on live parts of an installation.
Attention
A double isolated connection box may only be replaced by a
double isolated connection box. The double isolated
connection box cannot be replaced by a regular connection box
with automatic earthing.
Functional Description
The 5L4211 connection box is intended to be fitted with one
D0I fuse. The fuse capacity is limited to max 6A.
The phase to be connected to the fuse has to be chosen by the
black selection pin (screw type).
The connection
box is equipped with a ‘Surge protection
device’ (SPD) module.
Assembly
Attention
Remove the fuse during assembly of the connection boxes
1.
Ensure a safe working area during assembly, maintenance
and inspection of the connection box. Disconnect the power
of the primary circuit and make sure it cannot be enabled
unintentionally.
2.
Remove the transparent lid, fuse, selection pin and the
intermediate cover.
3.
Mount the connection box with the upper and lower
connection in the lighting pole.
4.
Remove the cover with SPD (pull off the mantle terminals).
There is a possibility to hook this on top of the connection
box.
5.
Connect the incoming and (if present) outgoing ground
cable to terminals N, 1, 2, 3.
6.
Replace the cover with SPD on the mantle terminals.
7.
For in-line connection of the SPD:
connect the outgoing
cable to the armature to terminals 6 and 7 (spring
connection)
For parallel connection of the SPD:
connect the outgoing
cable to the armature to terminals 4 and 5 (screw
connection)
8.
Tightly mount strain relief block.
9.
Check if the connections are mounted properly and firmly.
10.
Mount the intermediate cover and the selection pin.
11.
Install the fuse. Note: fuse type: D01 (E14), max 6A.
12.
Mount the transparent lid and screw tightly.
Incoming
Outgoing (SPD in-line)
N = Neutral
6 = Neutral wire to armature
1 = Phase L1
7 = Phase wire to armature
2 = Phase L2
3 = Phase L3
Outgoing (SPD parallel)
4 = Neutral wire to armature
5 = Phase wire to armature
If required, incoming terminals N, 1, 2 3 can also be looped to
the next lighting pole.
Attention
Terminal box is provided with phase selection: the phase to be
connected to the fuse has to be chosen by the black selection
pin (screw type).
Wiring Diagram
Maintenance and inspection
The connection box should be situated on a dry and clean
location.
The connection box should be mounted firmly.
The connections should be mounted firmly.
Indicator on SPD is on when power is switched on.
Attention
Always avoid working on live parts of an installation.
Disassembly instruction
1.
Disconnect the power of the main circuit and make sure it
cannot be enabled unintentionally.
2.
Unmount the transparent lid.
3.
Remove the fuse, selection pin and the intermediate cover
4.
Remove the strain relief block.
5.
Disconnect the armature cables.
6.
Remove the SPD
7.
Disconnect the ground cables
8.
Disconnect the connection box from the lighting pole.
Recycling
When the product has reached ‘end of life’, it must be recycled.
Do not dispose this product as unsorted municipal waste.
Contact a qualified recycler for disposal.
Always avoid working on live parts of an installation.
Attention
A double isolated connection box may only be replaced by a
double isolated connection box. The double isolated
connection box cannot be replaced by a regular connection box
with automatic earthing.
Functional Description
The 5L4211 connection box is intended to be fitted with one
D0I fuse. The fuse capacity is limited to max 6A.
The phase to be connected to the fuse has to be chosen by the
black selection pin (screw type).
The connection
box is equipped with a ‘Surge protection
device’ (SPD) module.
Assembly
Attention
Remove the fuse during assembly of the connection boxes
1.
Ensure a safe working area during assembly, maintenance
and inspection of the connection box. Disconnect the power
of the primary circuit and make sure it cannot be enabled
unintentionally.
2.
Remove the transparent lid, fuse, selection pin and the
intermediate cover.
3.
Mount the connection box with the upper and lower
connection in the lighting pole.
4.
Remove the cover with SPD (pull off the mantle terminals).
There is a possibility to hook this on top of the connection
box.
5.
Connect the incoming and (if present) outgoing ground
cable to terminals N, 1, 2, 3.
6.
Replace the cover with SPD on the mantle terminals.
7.
For in-line connection of the SPD:
connect the outgoing
cable to the armature to terminals 6 and 7 (spring
connection)
For parallel connection of the SPD:
connect the outgoing
cable to the armature to terminals 4 and 5 (screw
connection)
8.
Tightly mount strain relief block.
9.
Check if the connections are mounted properly and firmly.
10.
Mount the intermediate cover and the selection pin.
11.
Install the fuse. Note: fuse type: D01 (E14), max 6A.
12.
Mount the transparent lid and screw tightly.
Incoming
Outgoing (SPD in-line)
N = Neutral
6 = Neutral wire to armature
1 = Phase L1
7 = Phase wire to armature
2 = Phase L2
3 = Phase L3
Outgoing (SPD parallel)
4 = Neutral wire to armature
5 = Phase wire to armature
If required, incoming terminals N, 1, 2 3 can also be looped to
the next lighting pole.
Attention
Terminal box is provided with phase selection: the phase to be
connected to the fuse has to be chosen by the black selection
pin (screw type).
Wiring Diagram
Maintenance and inspection
The connection box should be situated on a dry and clean
location.
The connection box should be mounted firmly.
The connections should be mounted firmly.
Indicator on SPD is on when power is switched on.
Attention
Always avoid working on live parts of an installation.
Disassembly instruction
1.
Disconnect the power of the main circuit and make sure it
cannot be enabled unintentionally.
2.
Unmount the transparent lid.
3.
Remove the fuse, selection pin and the intermediate cover
4.
Remove the strain relief block.
5.
Disconnect the armature cables.
6.
Remove the SPD
7.
Disconnect the ground cables
8.
Disconnect the connection box from the lighting pole.
Recycling
When the product has reached ‘end of life’, it must be recycled.
Do not dispose this product as unsorted municipal waste.
Contact a qualified recycler for disposal.