Elektrogas VMH DN Series Manual Download Page 3

ELEKTROGAS – Technical Sheet  EE175 - 0117 

 

 3-16 

 

 

 

 

 

Description 

The VMH type valve is a safety shut off valve for gas with hydraulic actuator. It is suitable for air 

or  gas  blocking  and  releasing  controls,  required  in  the  main  pipe  of  gas  power  burners, 

atmospheric  gas  boilers,  industrial  kilns  and  others  gas  consuming  appliances.  

See Tab. 2 for maximum operative pressure for every model.   

 

 

 

Features 

The valves are made of aluminum alloy with a range for connections from DN 65 up to DN 300. 

 

Pipe connections meet group 2.   

Suitable for use with air and non-aggressive gases included in the 1

st

, 2

nd

 and 3

rd

 families (EN 

437). 

Special versions for aggressive gases. 

The valve is open only when energized: if, for any reason, power supply goes down, the valve 

closes immediately (intrinsic safe).  

Qualified for continuous service (100% ED).  

Size DN65-80 is equipped with flow rate adjustment. 

An  incorporated  fine  mesh  filter  protects  the  valve  seat  and  disc  as  well  as  downstream 

components and prevents dirty contamination. 

Provided  with  G1/4  pressure  gauge  on  two  sides  in  both  inlet  and  outlet  chamber  to  connect 

manometers, pressure switches, leakage tester or other gas equipments. 

The actuator is provided with ISO 4400 plug for easy cabling. The protection class is IP65 (EN 

60529). 

The actuator is provided with a led to visualize when it is energized. 

All  components  are  designed  to  withstand  any  mechanical,  chemical  and  thermal  condition 

occurring during typical service. Effective impregnation and surface treatments have been used 

to improve mechanical sturdiness, sealing and resistance to corrosion of the components. 

Valves are 100% tested and fully warranted. 

 

 

 

 

 

 

WARNING 

 This control must be installed in compliance with the rules in force. 

 

Summary of Contents for VMH DN Series

Page 1: ...delta elektrogas com VMH Safety shut off valves for gas with hydraulic actuator DN65 DN300 EE175 0117...

Page 2: ...s a brand name of ELETTROMECCANICA DELTA S p A Via Trieste 132 31030 Arcade TV Italy Tel 39 0422 874068 Fax 39 0422 874048 www delta elektrogas com info delta elektrogas com ELETTROMECCANICA DELTA S p...

Page 3: ...ntrinsic safe Qualified for continuous service 100 ED Size DN65 80 is equipped with flow rate adjustment An incorporated fine mesh filter protects the valve seat and disc as well as downstream compone...

Page 4: ...ches the end stop the pump is turned off and only the relief valve is consuming power If the power supply is shut off the relief valve opens and the disc closes rapidly interrupting the gas flow Fig 1...

Page 5: ...with special seals Technical specifications Tab 1 Connections Flanged PN16 ISO 7005 from DN65 to DN300 Voltage rating 15 10 230 VAC or 110 VAC 50 60 Hz Power consumption 20VA START 110 W Only for DN...

Page 6: ...18 14 VMH8 DN 80 1 6 10 15 92 0 60 200 305 350 536 160 8x18 14 VMH9 DN 100 1 3 15 25 152 0 40 250 350 366 571 180 8x18 18 VMH93 DN 125 0 5 25 40 250 0 30 310 460 461 671 210 8x18 34 VMH93U DN 125 1 3...

Page 7: ...7 16 AIR GAS V k V Gas flow chart Pressure drop Fig 4 Formula of conversion from air to other gases 15 C 1013 mbar dry Tab 3 Gas type Specific gravity Kg m GAS k 25 1 Air 1 25 1 00 Natural gas 0 80 1...

Page 8: ...in accordance with the characteristic Kvs value as shown in table 2 The selection of the valve requires the calculation of the Kv under the operating conditions Considering only subcritical pressure...

Page 9: ...ressure Equipment Directive 2014 68 UE ex 97 23 CE and the certification has been issued by the notified body CSI Spa 20030 Senago MI I Reg n CE 0497 PED 0497 2638 13 The following standards technical...

Page 10: ...or switch others on request They must be ordered with their code VMH 8 Valve type VMH Connections size and operative pressure 7 DN65 1 6bar 8 DN80 1 6bar 9 DN100 1 3bar 93 DN125 0 5bar 93U DN125 1 3ba...

Page 11: ...electrical voltage etc CAUTION Shut off the gas supply at the main manual shut off valve and disconnect electrical power to the valve before proceeding installation or servicing Fig 5 PIPING CONNECTI...

Page 12: ...ols only Avoid overtightening and mount tension free If the actuator has been removed check the correct position of the O ring and position the actuator on its connection flange in case of vertical pi...

Page 13: ...install on the valve because serious damage can result The continuous service 100 ED causes inevitable actuator heating depending of working environment This situation is absolutely normal and does n...

Page 14: ...ing is very easy with a 5mm Allen wrench remove the 1 8 plug on the side of the actuator and iintroduce the rod of PCS inside 1 8 hole and screw the switch with O ring Tighten using open ended spanner...

Page 15: ...PECTION Make this inspection when the valve does not work properly only To make an internal inspection of the valve do the following Shut ball valve upstream the system and make sure no pressure is in...

Page 16: ...attention to the O ring between actuator and valve 5 Reassemble the new one with inverse sequence If necessary replace the plug also WARNING To prevent product damage and dangerous situations read th...