background image

ED510- GAS DETECTOR     

 

ED510 IM REV 2 - 23.08.2017

7

WATER LEVEL DETECTION

The float switch should be mounted as low as possible in the bilge and requires approx. 5mm. of travel of the float to cause 

operate.

The ED735 float switches have 1K5 resistors in series with the switch and are potted in epoxy resin to prevent ingress of moisture 

etc. The switches are provided with 2m. of cable and as far as is practical this cable should run vertically upwards to a junction 

box (which should be waterproof) well above the possible level of bilge water. The final junction box should have a 4.7Kohm 

resistor fitted so that the main zone wiring can be monitored. N.B. The wires from the zone line junction box to the switch are not 

fault monitored and should therefore be tested at regular intervals. Sensors with E.O.L resistor fitted can be used to give fault 

monitoring of last sensor.

On completion of installation it is important that both short circuit and open circuit faults are simulated and correct alarm operation 

checked.  In addition the float switches should be checked by immersing in water. Lifting the float manually does not check float 

buoyancy!

The magnetic circuit within the float allows either normally closed or normally open operation. The float has been set during 

manufacture to give a normally open condition when in the lower position. Thus when the float is raised the circuit will be made 

and the 1.5Kohm resistance will be connected across the zone line.  If necessary for special applications the float switch may be 

reversed thus giving normally closed operation.

AUTOMATIC BILGE PUMPING

Each zone has voltage free 2A@ 30VDC non inductive load contacts which can be used for the automatic operation of bilge 

pumps. An external relay suitably rated will be required for bilge pumps taking in excess of 2A. The onboard relay can also be 

used to operate a Xenon Beacon mounted externally (as high as possible). Alerting other boat users etc. when the vessel is 

unmanned.

WIRING TYPICAL FLOAT SWITCHES

Control unit 

zone terminals

ED735 float switches

4K7

E.O.L

Summary of Contents for ED510

Page 1: ...lectronic devices co uk MANUFACTURED IN MALVERN ENGLAND BY ELECTRONIC DEVICES LIMITED ALARM FAULT TEST ON ALARM O C FAULT S C FAULT ALARM O C FAULT S C FAULT TEST OFF TEST ALARM RESET ALARM FAULT TEST ON TEST OFF HIGH ALARM LOW ALARM FAULT VALVE ON HIGH ALARM LOW ALARM FAULT VALVE OFF POWER SOUNDER CCT FAULT VALVE ON MUTE MULTIFUNCTION ALARM SYSTEM TYPE ED510 FIRE LEVEL GAS ZONE 1 ZONE 2 ZONE 1 ZO...

Page 2: ... PROCEEDURE 12 GENERAL FEATURES 3 PAGE INSTALLATION 5 USER OPERATION 4 TEST PROCEEDURE SETUP 9 PRINTED CIRCUIT BOAD LAYOUT 13 CUTOUT TEMPLATE 14 CONTROL PANEL 5 FIRE DETECTION 5 CHOOSING THE CORRECT DETECTORS 5 WIRING TYPICAL DETECTORS 6 WATER LEVEL DETECTION 7 AUTOMATIC BILGE PUMPING 7 WIRING TYPICAL FLOAT SWITCHES 7 GAS DETECTION 8 EDP SEMICONDUCTOR GAS SENSORS 8 AUDIABLE AND VISUAL ALARMS 8 CON...

Page 3: ...tection system operating from a nominal 12 or 24VDC supply depending upon model FEATURES Two fire detection zones fault monitored Two water level detection zones fault monitored Two gas detection sensor inputs fault monitored Two bilge pump outputs with manual override Automatic gas solenoid valve shut off Semiconductor Catalytic or Electrochemical gas sensors may be fitted Sounder beacon output f...

Page 4: ...MUTE button will turn off the sounders and beacons including the internal buzzer However the zone light will remain on until the float switch has deactivated and the RESET button is pressed Also if the other fire zone or a gas or bilge alarm occurs the sounders and beacons will re alarm If you need to manually activate the bilge pumps this can be achieved by pressing the appropriate level zone TES...

Page 5: ... item on a zone reduces the risk of it being out of circuit due to head removal or wiring faults CHOOSING THE CORRECT DETECTORS The types of detector required varies for each location Guidance should be sought from classification societies and SOLAS regulations For general use two types of smoke detector are recognised by standards as good general purpose fire detectors offering a high level of pr...

Page 6: ... 5 6 2 1 3 4 5 6 4K7 EOL REMOTE INDICATOR REMOTE INDICATOR YBO R 5M YBO R 5M YBO R 4M YBO R 4M 4K7 EOL APOLLO ORBIS L E D O U T 4 APOLLO ORBIS L E D O U T 4 APOLLO ORBIS L E D O U T 4 4K7 EOL REMOTE INDICATOR L1 L2 L R L1 L2 L R 4 3 2 1 REMOTE INDICATOR REMOTE INDICATOR NOTE ...

Page 7: ...ort circuit and open circuit faults are simulated and correct alarm operation checked In addition the float switches should be checked by immersing in water Lifting the float manually does not check float buoyancy The magnetic circuit within the float allows either normally closed or normally open operation The float has been set during manufacture to give a normally open condition when in the low...

Page 8: ...emiconductor gas sensor is fitted the low alarm and high alarm LEDs will illuminate within a few seconds Press the MUTE button to silence the sounders The ED510 will be ready to reset in a few minutes once the gas sensors have reached their correct operating temperature and provided they are in clean air Provided all connections are correct the ED510 should have its power light only illuminated Si...

Page 9: ...r correct operation after installation and then regularly as part of routine maintenance Additionally its is important to check the correct operation of fault monitoring An open circuit fault can easily be achieved by removal of a detector Ensure the appropriate fault light and the internal buzzer operate All EDL call points come complete with a test key enabling testing without the need to break ...

Page 10: ...d diagram below The time period between the level switch operating and the alarm being raised can be adjusted for each zone using the adjustable ON DELAY potentiometer A clockwise turn increases the ON DELAY See printed circuit board diagram below Each zone can be manually put in to alarm and therefore operating the bilge pump by pressing the TEST ON button The TEST OFF button can be pressed to tu...

Page 11: ...tes prematurely then decrease sensitivity by rotating potentiometer clockwise while repeatedly pressing the RESET button on the ED510 front panel until the A1 LED goes out then turn slowly anti clockwise again until it just illuminates 4 Repeat step 4 for the A2 high alarm calibration on the same sensor calibration with the following alterations i Use the correct gas for your A2 high alarm ii Use ...

Page 12: ...light illuminates prematurely then decrease sensitivity by rotating potentiometer clockwise while repeatedly pressing the RESET button on the ED510 front panel until the A1 LED goes out then turn slowly anti clockwise again until it just illuminates 6 Repeat step 4 for the A2 high alarm calibration on the same sensor calibration with the following alterations i Use the correct gas for your A2 high...

Page 13: ...ARM ON DELAY ADJUST RUN ON DELAY ADJUST RUN ON DELAY ADJUST SEN1 VE FUSED OUT VE VE VE VE S VE NO NC C NO NC C NO NC C C NC BR G Y BL BR G Y BL VE S VE VE VE VE VE VE VE SWITCH UP POSITION EDN HEAD ELECTRONICS 4C 5C or 7C SWITCH DOWN POSITION EDP SEMICONDUCTOR 1B 2B or 3B SEN2 VR3 VR6 VR5 VR4 LEVEL ZONE 2 LEVEL ZONE 1 LEVEL ZONE 1 RELAY OUTPUT GAS VALVE OUTPUT CONNECTIONS GENERAL ALARM SOUNDER OUT...

Page 14: ...ED510 GAS DETECTOR ED510 IM REV 2 23 08 2017 14 108 238 4 5 2 L E N A P T N O R F T U O T U C T U O T U C T U O T U C T U O T U C 7 7 7 FRONT PANEL 130 ...

Reviews: