Exhaust duct
It is recommended that each dryer be
connected separately to a smooth air outlet pipe
with the lowest possible friction.
If more than one dryer is connected to the same
outlet pipe, the pipe diameter must be
increased after each dryer, just as all dryers
must be equipped with a back draft damper to
prevent humid air from running back into dryers
that are not in operation.
The pipe must end outside in the open. The
outlet must be protected against rain, foreign
objects and prevailing winds.
Note! In cold areas, condensation may cause
frost damage to the building.
Gentle bends
To keep the air fl owing, ensure proper dryer
operation, and minimise lint buildup in the
exhaust system, never connect ducts at right
angles, always use gentle bends.
Service organisation/dealer
If you have questions relating to the design of
the exhaust system, please contact your local
dealer or service organisation.
Installation
No. of dryers
Outlet
m
3
/h
d
mm
Fresh-air intake
cm
2
Pipe length 0-70 m
d
1
290 Ø125
400
Ø125
2
440
Ø125
800
Ø160
3
660
Ø125
1200
Ø200
4
880
Ø125
1600
Ø250
Fig
4
Fig
3