
electrolux
installation instructions 35
Installation instructions
IMPORTANT – Safety requirements
Where applicable Natural Gas and L.P
Gas versions of this appliance are
available. Check that this model is
suitable for the type of supply available.
This appliance must be installed and/or
serviced by a competent person in
accordance with the Gas Safety
(Installation and Use) Regulations Current
Editions and the I.E.E. Wiring Regulations.
For appliances installed in the Republic
of Ireland please refer to NSAI - Domestic
Gas Installation IS813 Current Editions
and the ETCI Rules for Electrical
Installations.
In the Republic of Ireland a signed
Declaration of Conformity is issued by the
installer (IS813 Currents Editions Annex
D.1).Detailed recommendations are
contained in the following British
Standard Codes of Practice – BS.6172,
BS.5440: Part 2 and B.S.6891. All British
Standards must be ‘Current Editions’.
This appliance must be installed
by a qualified electrician / competent
person (CORGI Registered). Safety
may be impaired if installation is not
carried out in accordance with these
instructions.
Before connecting the appliance
make sure that the voltage of your
electricity supply is the same as that
indicated on the rating plate.
This is situated on the lower front
frame of the appliance and can be
seen upon opening the door.
Alternatively the rating plate may
also be found on the back or top of
some models (where applicable).
Do not alter the electrical circuitry
of this appliance.
Provision for ventilation
This appliance is not connected to a
combustion products evacuation device.
It shall be installed and connected in
accordance with the current installation
regulations. Particular attention shall be
given to the relevant requirements
regarding ventilation.
The room containing the appliance
should have an air supply in accordance
with BS.5440: Part 2 Current Edition. All
rooms require an openable window or
equivalent and some rooms will require a
permanent vent as well. For room
volumes up to 5m
3
an air vent of 100cm
2
is required: for room volumes between
5m
3
and 10m
3
an air vent of 50cm
2
is
required. If the room has a door that
opens directly to the outside, no air vent
is required.
For room volumes that exceed 11m
3
no air vent is required. If there are other
fuel burning appliances in the same room,
BS.5440: Part 2 Current Edition should
be consulted to determine the requisite
air vent requirements.
Prolonged intensive use of the
appliance may call for additional
ventilation, for example opening a
window, or more effective ventilation, for
example increasing the level of
mechanical ventilation where present.