background image

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

When using the vacuum pump

For method of using a manifold valve, refer to its operation manual.

1.  Completely tighten the flare nuts, 

A, B, C, D, connect the manifold 
valve charge hose to a charge port 
of the low-pressure valve on the 
gas pipe side.

2.  Connect the charge hose 

connection to the vacuum pump.

3.  Fully open the handle Lo of the 

manifold valve.

4.  Operate the vacuum pump to 

evacuate. After starting 
evacuation, slightly loose the flare 
nut of the Lo valve on the gas pipe 
side and check that the air is 
entering (Operation noise of the 
vacuum pump changes and a 
compound meter indicates 0 
instead of minus)

5.  After the evacuation is complete, 

fully close the handle Lo of the 
manifold valve and stop the 
operation of the vacuum pump. 
Make evacuation for 15 minutes or 
more and check that the 
compound meter indicates -
76cmHg (-1x10 Pa).

6.  Turn the stem of the packed valve 

B about 45o counterclockwise for 
6~7 seconds after the gas coming 
out, then tighten the flare nut 
again. Make sure the pressure 
display in the pressure indicator is 
a little higher than the atmosphere 
pressure.

7.  Remove the charge hose from the 

Low pressure charge hose.

8.  Fully open the packed valve stems 

B and A.

9.  Securely tighten the cap of the 

packed valve.

27 electrolux 

electrical work

Electrical safety

Perform the electric safe check after completing installation:

Gas leak check

Soap water method

Apply a soap water or a liquid neutral 
detergent on the indoor unit 
connection or outdoor unit 
connections by a soft brush to check 
for leakage of the connecting points 
of th piping. If bubbles come out, the 
pipes have leakage.

Leak detector

Use the leak detector to check for 
leakage.

Caution

A: Lo packed valve, B: Hi packed 
valve C and D are ends of indoor unit 
connection.

1. Insulated resistance: The insulated resistance must be more than 2M    .
2. Grounding work: After finishing grounding work, measure the grounding 

resistance by visual detection and grounding resistance tester. Make sure the 
grounding resistance is less than 4    .

3. Electrical leakage check (performing during test running): During test 

operation after finishing installation, the serviceman can use the electroprobe 
and multimeter to perform the electrical leakage check. Turn off the unit 
immediately if leakage happens. Check and find out the solution ways till the 
unit operate properly.

electrical safety

 electrolux 28

Cover

indoor unit
check point

Outdoor unit
check point

Summary of Contents for EASC09P5AHLW

Page 1: ...PLIT TYPE ROOM AIR CONDITIONER MODELS Please read this manual completely before operating your room air conditioner 1300807A S5 20 23 EM_ENGLISH R410a_50Hz EAS C E 09P5AHLW EAS C E 12P5AHLW EAS C E 18P5AHLW EAS C E 24P5AHLW ...

Page 2: ...ith the rest of your domestic garbage Instead please take the appliance to the nearest WEEE collection point where available The air conditioner you purchased has R410a gas refrigerant a environmental friendly gas which does not damage the ozone layer Environmental Advices Welcome to the world of simple handling and no worries 01 electrolux welcome Contents contents electrolux 02 Welcome 01 Enviro...

Page 3: ...ectric shock 5 Keep firearms away It may cause fire 6 Do not operate or stop the unit by switching on or off the power It may cause electric shock or fire due to heat generation 7 Do not operate with wet hands or in damp environment It may cause electric shock 8 Do not allow water to run into electric parts It may cause failure of machine or electric shock 9 Do not drink water drained from air saf...

Page 4: ...ay cause an electric shock 05 electrolux safety precautions 20 Ventilate the room well when used together with a stove etc An oxygen shortage may occur 21 When the unit is to be cleaned switch off and turn off the circuit breaker Do not clean unit when power is on as it may cause fire and electric shock it may cause an injury 22 Do not put a children pet or house plant where it will be exposed to ...

Page 5: ...with machine oil 2 Sites with a high concentration of salinity such as coastal areas 3 Sites with sulfuric gas such as hot water springs 4 Sites with high frequency equipment such as wireless equipment welding machines and medical installations 5 Sites with flammable gases or volatile material 6 Sites with special environmental conditions 7 Laundry rooms Indoor Unit 1 The unit must be installed at...

Page 6: ...n 5 meters 16 feet and for pipes measuring at least 10 meters 33 feet in length 7 The site must provide enough space around the unit as shown in the diagram 8 Children must not be able to access the installation site More than 60cm More than 30cm More than 200cm More than 30cm More than 60cm 09 electrolux outdoor unit Parts list NUMBERING PART NAME Installation plate Clip anchor Self tapping screw...

Page 7: ... 2 3 1 Indoor unit Outdoor unit 6 6 More than 12cm More than 12cm Air filter More than 200cm More than 60cm More than 30cm More than 60cm More than 15cm A B C 11 electrolux parts list Indoor unit installation Installation plate description indoor unit installation electrolux 12 2 3m or more 45 41 45 41 45 ...

Page 8: ... of drain hose into water Do not block water flow by a rise Connective pipe and drainage installation Drainage 1 Run the drain hose sloping downward Do not install the drain hose as illustrated below 2 When connecting extension drain hose insulate the connecting part of extension drain hose with a shield pipe do not let the drain hose slack 13 electrolux indoor unit installation Connective pipe in...

Page 9: ...tion where the discharged air is not blocked In the case that the installation place is exposed to strong wind such as a seaside make sure the fan operating properly by putting the unit lengthwise along the wall or using a dust or shield plates 3 Specially in windy area install the unit to prevent the admission of wind If need suspending installation the installation bracket should accord with tec...

Page 10: ... leakage is due to defect in the flaring work Carry out correct flaring work using the following procedure 1 Cut the pipes and the cable A Use the piping kit accessory or pipes purchased locally B Measure the distance between the indoor and the outdoor unit C Cut the pipes a little longer than the measured distance D Cut the cable 1 5m longer than the pipe length 2 Burr removal A Completely remove...

Page 11: ...e technicians should refuse to install the air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times capacity of Max Current of the unit should be installed in power circuit 4 Ensure the air conditioner is grounded well 5 According to the attached Electrical...

Page 12: ...lux 22 Before performing any electrical work turn off the main power to the system 1 The inside and outside connecting cable can be connected without removing the front grille 2 The indoor power cord type is H05VV F or H05V2V2 F the outdoor power cord and interconnected cord type is H07RN F 3 Lift the indoor unit panel up remove the electrical box cover by loosening the screw 4 Ensure the colour o...

Page 13: ...e terminal block of indoor and outdoor units 3 Secure the cable onto the control board with the cord clamp 4 To prevent the ingress of water form a loop of the connective cable as illustrated in the installation diagram of indoor and outdoor units 5 Insulate unused cords conductors with PVC tape Process them so they do not touch any electrical or metal parts Connect the cable to the outdoor unit S...

Page 14: ...sure in the system rises 2 Operating current rises 3 Cooling or heating efficiency drops 4 Moisture in the refrigerant circuit may freeze and block capillary tubing 5 Water may lead to corrosion of parts in the refrigeration system 6 Therefore the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system ...

Page 15: ...le higher than the atmosphere pressure 7 Remove the charge hose from the Low pressure charge hose 8 Fully open the packed valve stems B and A 9 Securely tighten the cap of the packed valve 27 electrolux electrical work Electrical safety Perform the electric safe check after completing installation Gas leak check Soap water method Apply a soap water or a liquid neutral detergent on the indoor unit ...

Page 16: ...l the device 2 Guarantee that the unit is appropriately fastened and complies with all of the aforementioned safety norms 3 Before operating the air conditioner ensure that the air filter is installed correctly 4 If the unit has been out of use for a long period of time it is recommended that the air filter be cleaned before use During continuous use clean the air filter every two weeks 5 This air...

Page 17: ... for explanation purpose only They may be slightly different from the air conditioner you purchased 31 electrolux product description The description in the control is based on a typical model The functions are the same in your air conditioner even if there are some differences in the appearance Display panel indoor unit 13 16 14 15 product description electrolux 32 Front panel frame Front panel A...

Page 18: ... Replace the batteries when there is no receiving beep from the indoor unit or if the transmission indicator on the remote controller fails to light 2 The remote controller is powed by two dry batteries R03 LR03X2 housed in the rear part and protected by a cover 3 Remove the cover by pressing and sliding off 4 Remove the old batteries and insert the new batteries placing the and ends correctly 5 R...

Page 19: ...and the control will return to the initial settings 1 2 3 4 TEMP Push the button to increase setting temperature or to increase Hour during Timer setting Push the button to decrease setting temperature or to decrease Hour during Timer setting FAN SPEED Used to select the Fan Speed in four steps AUTO LOW MED or HIGH Each time the button is pressed the fan speed mode is shifted TIMER ON Press this b...

Page 20: ...ll operate at a setting temperature of 8 C The display window of indoor unit will display FP Press the buttons of ON OFF SLEEP FP MODE FAN SPEED UP DOWN and SHORTCUT while operating will cancel the FP LED Disable Active indoor screen Display When pushing more than 2 seconds the FOLLOW ME function will be activated pushing more than 2 seconds again to disable LOCK When you press the recessed LOCK b...

Page 21: ...t the cooling or heating effect of the air conditioner it would automatically change the swing moving direction Turbo self clean function Press this button less than 2nds will initiate TURBO function And if keep pressing this button more than 2nds the SELF CLEAN function is initiated Turbo function enables the unit to reach the preset temperature in the shortest time When press this button on cool...

Page 22: ...ner will automatically start operating at the set time Example To start the air conditioner in 6 hours 1 Press the TIMER ON button the last setting of starting operation time and the signal h will show on the display area 2 Press the TIMER ON button to display 6 0h on the TIMER ON display of the remote controller 3 Wait for 3 seconds and the digital display area will show the temperature again The...

Page 23: ...FORCED COOL and DRY mode Before selecting the function it is recommended to run the air conditioner under cooling operation for about half an hour Once the Self Clean function is activated all TIMER setting will be cancelled During SELF CLEAN operation when pressing the SELF CLEAN button on the remote controller again the unit will stop the operation and turn off the unit automatically COMBINED TI...

Page 24: ...n To automatically swing the air flow direction up down Perform this function while the air conditioner is in operation Lever how to use the indoor unit electrolux 46 Clean air function optional Improving the quality of indoor air is one of the purposes of an air conditioner This air conditioner is equipped with ionizer or Plasma Dust Collector Depending on specific configuration of the model With...

Page 25: ...oo small as COOLING or HEATING performance may be impaired due to too restricted air flow area Do not operate unit with horizontal louver in closed position When the air conditioner is connected to power initial power the horizontal louver may generate a sound for 10 seconds this is a normal operation 47 electrolux how to use the indoor unit Manual operation without remote control Manual operation...

Page 26: ...once a month and replace every 4 to 5 months Use a vacuum cleaner filtro de aire filtro de aire 49 electrolux maintenance then dry 6 Clean the support frame using a vacuum cleaner or water After dry for a couple of hours or until dry 7 Insert the fresh air filter in its original place 8 Insert the high part of the air filter fresh air filter Support frame again in the unit keeping in mind that the...

Page 27: ...normal condition when the air conditioner has not been used for a long time or during first use of the unit 51 electrolux operation tips A peculiar smell comes out from the indoor unit This is caused by the indoor unit giving off smells permeated from building material from furniture or smoke The air conditioner turns to FAN only mode from COOL or HEAT For cooling and heating models only mode When...

Page 28: ...and connecting the unit 2 Frequent change of fuses and malfunctions in the switch circuit 3 Water spills over the equipment 4 Remote control does not work 5 Any other abnormal situation If your air conditioner malfunctions check the following information to find solutions or probable causes of the failure Do not try to repair the unit by yourself if these solutions do not solve the failures call y...