electrolux
13
max. 140
4/6=
508
5/6=
635
0-50
319 200
6/6=
762
17 ( Griff )
1629
49
5/6=
635
1502
325
Removable
rear panel
138
2050
150
150
495
150
548
598
550
600
100
A 319
N 330
Installation Instructions
Safety instructions
Caution!
The minimum safety gap bet-
ween the hob and the extractor hood
must be 50 cm in the case of electric
hobs, and 70 cm in the case of gas
hobs.
The appliance must be disconnec-
ted from the mains supply when being
serviced; pull out the mains plug. The
general directives for the operation of
electrical appliances, the regulations of
the responsible electricity supply com-
panies and provisions of these installati-
on instructions are to be followed to the
letter.
The incorrect installation of an extractor
hood may lead to a fire. The canton fire
brigade regulations are also to be ob-
served.
The risk-free operation of appliances
(e.g chimney, gas cooker) and extrac-
tor hoods jointly connected to a single
flue is only guaranteed if the room and/
or apartment are ventilated from outside
by means of a suitable air inlet aperture
of approx. 500-600 sq cm, and hence
negative pressure is avoided when the
extractor hood is in operation. The ne-
gative pressure in the room must not be
greater than 4 Pa.
The extracted air has to be drawn off
through a separate pipe to the open air.
It should not be passed into a chimney.
If this principle is not observed, a drastic
loss of performance and increased ope-
rating noise are to be expected.
Installation for exhaust extraction
The vapours occurring above the hob are
cleaned in the grease filters and led via an
exhaust duct into the open air.