16
Extraction
The charcoal fi lter is not required in this mode and
should be removed.
Ducting
The ducting used must be Ø150mm (6ins), or
Ø125mm (5ins) in diameter.
If possible duct through the wall immediately above
the hood body.
For the best performance use the shortest possible
duct run and the minimum number of bends.
Where fl exible ducting is fi tted it should not be
turned through very tight bends as this may impair
the performance of the hood.
It is recommenmded a maximum length of 3 metres,
to be installed, to be reduced 1 metre for each 90
o
bend installed in the ducting run.
If the distance is greater than 3 metres the effi cency
of the hood could be impaired.
The diameter of the ducting spigot on the top of the
hood body item 1 is Ø150mm (6”).
When using Ø125mm (5”) ducting it will be
necessary to install the ducting adapter
item 9
to
the Ø150mm (6”) outlet on the top of the hood body
and the Ø120mm to 125mm ducting collar
item 10
(supplied).
If the room where the cooker hood is to
be used contains a fuel burning appliance
such as a central heating boiler, then its fl ue
must be of the room sealed or balanced fl ue
type.
If other types of fl ue or appliances are fi tted
ensure that there is an adequate supply of
air to the room.
The cooker ducting (extraction mode) must
never be connected to central heating fl ues,
radiators or water heaters etc.
Electrical Connection and Working
Test
Before fi tting the chimney to the canopy make the
electrical connection as described in the section
titled “ELECTRICAL CONNECTION”.
When the electrical connection has been made, test
the three speed fan and worktop illumination.
9
ø 150
ø 125
10
INSTALLING THE COOKER HOOD