03/31/2015 2
EI907
Product Configurator
EM-MA10-240-1-10
Option
Collar
Size
A =
06 = 6”
X = No Damper
08 = 8”
10 = 10”
kW
14 = 14”
01 = 1 kW
02 = 1.6 kW
Phase
05 = 5 kW
1 = Single phase
10 = 10 kW
3 = Three phase
15 = 15 kW
20 = 20 kW
Volts
14 = 14 kW
120 = 120-volt
22 = 22 kW
240 = 240-volt
208 = 208-volt (3-phase)
Specification Tables
Temperature Rise & CFM Chart
(this model series)
Model
SINGLE PHASE MODELS
MA01
MA02
CFM
CFM
Required
Temp
Rise
80° F
39
63
70° F
45
72
60° F
53
84
50° F
63
101
40° F
79
126
30° F
105
168
Specifications
Model
kW
Btu/h
Amps
Internal
CB
Motor
FLA
Motor
HP
Phase
Voltage
CFM
Max Fuse/
HACR
Duct
Connection
Shipping
Weight
Max
Static
EM-MA01-120-1-06 1 3,410 8.3
N/A
0.5 1/16 1-50/60 120
150 0.03”
15
6”
31
EM-MA02-120-1-06 1.6 5,460 13.3
N/A
0.5
1/16 1-50/60 120
150 0.03”
20
6”
32
EM-MA05-240-1-08 5 17,070 20.8 N/A
0.4 1/10 1-50/60 240
350 0.03”
30
8”
59
EM-MA10-240-1-10 10 34,150 41.6
N/A
0.8
1/5 1-50/60 240 625 0.03”
60
10”
65
EM-MA15-240-1-14
15
51,220
62.4
60 + 30
1.7
1/3
1-50/60
240
1050
0.25”
90
14”
115
EM-MA20-240-1-14
20
68,300
83.2
60 + 60
2.5
1/2
1-50/60
240
1200
0.25”
120
14”
120
EM-MA14-208-3-14 14.4 49,170 40.0
50
1.7
1/3
3-50/60
208
900
0.25”
50
14”
115
EM-MA22-208-3-14
21.6
73,760
60.0
50 + 30
2.5
1/2
3-50/60
208
1250
0.25”
80
14”
125
Summary of Contents for Make-Up Air II EM-MA01