C: Using the IEC61850 Protocol Ethernet Network Server
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
C.2.2: Configuring the IEC 61850 Protocol Ethernet Network Server
You need to configure the IEC 61850 Protocol Ethernet Network server for communi-
cation, both from the standpoint of the device (the Device Profile) - see Section
C.2.2.1: Configuring the Device Profile IEC 61850 Protocol Ethernet Network Server
Settings on page C-21, and of the network (the SCL configuration file, which is a .cid
file uploaded to the meter) - see Section C.2.2.2: Configuring the Meter on the IEC
61850 Network on page C-25.
C.2.2.1: Configuring the Device Profile IEC 61850 Protocol Ethernet
Network Server Settings
You use the Communicator EXT™ application to set the card’s network parameters,
including the IEC 61850 and GOOSE features. Basic instructions are given here, but
you can refer to the Communicator EXT™ software User Manual for additional infor-
mation. You can view the manual online by clicking Help>Contents from the Commu-
nicator EXT™ software main screen.
1. Using Communicator EXT™ software, connect to the meter through its USB port,
RS485 serial port, or Ethernet 2 port (see Chapter 5 for instructions on connecting
to your meter with Communicator EXT™ software).
2. Click the Profile icon to open the meter’s Device Profile screen The profile is
retrieved from the Nexus® 1500+ meter. Double-click General Settings,