background image

 

 

Fig. 5 — Air Cleaner Schematic (with Air Proving Switch) 

Electronic Air Cleaner Installation 

1.  Remove  existing  equipment  filter.  Thoroughly  clean 

fan compartment and ductwork where Air Cleaner is 
to be installed. 

2.  Open  access  door.  Slide  filters  and  collecting  cells 

out of cabinet. 

3.  Place  cabinet  in  ductwork.  Holes  are  provided  to 

attach  cabinet  to  ductwork  or  equipment.  If  the 
adjoining  ductwork  is  flanged,  install  the  screws  so 
that the screw heads are inside the cabinet. This will 
help  prevent  damage  to  prefilter  and  carbon  filters 
during  removal  for  cleaning. 

Never

  put  screws  or 

rivets 

into 

the 

removable 

power 

box. 

When  the  air  duct  does  not  fit  the  Air  Cleaner 
opening,  a  gradual  transition  is  recommended  to 
reduce air turbulence though the air Air Cleaner and 
to  increase  its  efficiency.  There  should  not  be  more 
than  20º  of  expansion  used  on  each  side  of  the 
transition fitting. Do not reduce ductwork to a smaller 
Air Cleaner or it will increase the velocity of airflow. 

4.  If the Air Cleaner is installed adjacent to an elbow or 

angle  fitting,  turning  vanes  are  recommended  to 
improve air distribution across the collecting cells. 

5.  After the Air Cleaner has been installed, seal seams 

airtight  with  duct  tape  or  caulking  to  prevent  dust 
from entering the system. 

6.  Replace the prefilters in the track on the air entering 

side.  Place  the  carbon  filters  evenly  spaced  in  the 
track  on  the  air  exiting  side.  The  collecting  cells  are 
placed  between  the  tracks,  with  the  arrow  on  cell 
pointing  towards  the  fan.  The  cell  handle  may  need 
to  be  repositioned  if  the  airflow  is  in  a  different 
direction  than  the  left  to  right  set  up.  The  handle 
should face the door. Close access door. 

 
Wiring 

 

Wiring  should  only  be  performed  by  qualified 

personnel only. All wiring must comply with all applicable 
codes  and  standards.  The  voltage  of  the  power  source 
must match the voltage indicated on the Air Cleaner. The 
Air Cleaner must operate 

ONLY

 when the system fan is 

running. Make sure the Air Cleaner is properly grounded. 

If  the  air  cleaner  is  equipped  with  a  cord  and  plug, 

the air cleaner can be plugged into an outlet within 6 feet 
of  the  unit.  Do  not  use  an  extension  cord  if  the  outlet  is 
too  far  away.  Have  an  electrician  wire  in  a  new  outlet 
closer to the air cleaner.   

If  the  air  cleaner  is  not  equipped  with  a  cord,  then 

wire  the  Air  Cleaner  directly  to  a  120  V  power  source 
preferably to the same source that is supplying power to 
the  furnace  or  air  handler.  The  APS  will  power  the  Air 
Cleaner  when  there  is  sufficient  airflow  to  activate  the 
sensor. See Fig 5. 

Note:

  The  power  switch  will  be  lit  even  if  there  is  no 

airflow. 

If the unit  is to be  wired to the EAC contacts on the 

system  module,  check  that  there  is  sufficient  voltage  to 
the EAC contacts with the fan operating in all conditions. 
Some systems do not power the contacts on low speed. 
 

SYSTEM CHECK 

Perform the following system check before operation. 
1.  Replace  prefilters,  collecting  cells  and  carbon  filters. 

Close access door. 

2.  Turn  Air  Cleaner  power  switch 

ON

.  Ensure  system 

fan  is  operating.  Both  the  power  switch  light  and 
performance  indicator  light  should  be  lit.  The  power 
switch light indicates the Air Cleaner has unit voltage. 
The  performance  indicator  light  shows  that  the  Air 
Cleaner is operating. 

WARNING  

Electrical  shock  can  cause  injury  or  death.  Be  certain 
main line disconnect switch is off before wiring.  

Summary of Contents for EASASD-10ASC

Page 1: ...rease mold fungi bacteria viruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated...

Page 2: ...of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 re...

Page 3: ...the Air Cleaner will vary with CFM and whether the carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fan compartment...

Page 4: ...ifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Whenever p...

Page 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applica...

Page 6: ...a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and...

Page 7: ...igh Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells installed the door closed and the sy...

Page 8: ...e performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor is properly set down to t...

Page 9: ...ner 8 Remove the high voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high...

Page 10: ...olding the power box to the cabinet 5 Slide the power box forward then up to remove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to...

Page 11: ...options with power box 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0603 15 Collecting Cell D0 0...

Page 12: ...making good connection on cell With needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet fro...

Page 13: ...basis for the Air Cleaner to function at its peak of efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below...

Page 14: ...NOTES 14...

Page 15: ...pairing removing installing shipping servicing or handling of either defective parts or replacement parts Such costs may be covered by a separate warranty provided by the dealer LIMITATIONS OF WARRANT...

Page 16: ...of the furnace or air handler ensure that there is 115 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage...

Reviews: