OPERATION
Automatic charging
in three phases:
•
3A rapid charge (current control), until 13,4 V (26,8 V) is reached in the battery.
•
Intermediate charging via voltage control, until 13,5 V (27 V) is reached in the
battery.
•
Charge maintenance using a very low current value, but sufficient to maintain
the voltage value at 13,5 V (27 V).
The
green indicator (LED)
is only lit when the following conditions happen at the
same time:
•
mains on;
•
battery voltage above 65% (+/- 10%) of nominal value.
The
red indicator (LED)
is only lit when at least one of the following conditions
happens:
•
battery voltage above 65% (+/- 10%) of nominal value;
•
polarity inversion;
•
battery terminals short-circuit.
If there is overloading of the remote repetition terminals or if there is a mains
failure, both of the indicators will remain unlit.
The
remote signals repetition
is available on terminals 11, 12 and 14:
The load connected between terminals 11 and 12 is supplied when the
green
indicator is lit
;
The load connected between terminals 11 and 14 is supplied when the
red
indicator is lit
;
Measures in accordance with CEI-EN60335-2-29
Continuous line = initial characteristic
Broken line = work characteristic
TYPICAL LOAD CURVES