VIP 396 ADDITION TO THE INSTRUCTION MANUAL
ADDITIONAL PAGES PROVIDED IN THE SET-UP MENU OF THE VIP396 MODELS EQUIPPED WITH OUTPUT
OPTIONS
In the set-up menu of the models VIP396 485 (with Rs485 serial output), VIP396 4-20mA 485 (with two 4-20mA or 0-20mA
analog outputs and a Rs485 serial port) and VIP396 ALM 485 (with two relay outputs which can be used as pulsated outputs
or as alarm outputs or controlled in the remote mode via Rs485), the additional pages described here below are provided at
the end of the standard model pages.
VIP396 ALM 485 -
VIP396 4-20mA 485
[Fig. 1 ]
With the SEL key, the parameter to modify can be selected: the selected parameter will flash.
With the SET key, the selected parameter can be modified.
The PAG key enables to go to the next page.
The Baud rate (3 top digits) can have the following values: 2.4, 4.8, 9.6, 19.2 (kbaud).
The Parity (central) value can be : N(none), O(odd), E(even).
The type of communication protocol Modbus (3 bottom digits) can be:
ASCII = Modbus ASCII
BCD = Modbus BCD
IEEE = Modbus IEEE standard, INTEL format
Pressing the PAG key enables to go to the address selection page.
[Fig. 2 ]
With the SEL key, the (flashing) digit to modify can be selected.
With the SET key, the selected digit can be modified.
The permitted address field ranges between 1 and 247.
The PAG key enables to go to one of the following pages, according to the VIP396 model:
measurement page
(model VIP396 485);
4-20mA set-up page
(model VIP396 4-20mA 485);
relay set-up page
(model VIP396 ALM 485).
. VIP396 4-20mA 485
[Fig.3 VIP396 4-20mA 485]
By pressing the SET key, the type of output (either 4-20mA or 0-20mA) can be selected.
Pressing the PAG key enables to go to the measure selection page corresponding to output 1.
[Fig.4 VIP396 4-20mA 485]
Output 1 measure selection
By pressing the SET key one of the following measures can be selected for output 1:
V total (3 PH, 2 PH or 1 PH according to the instrument set-up)
A total (3 PH, 2 PH or 1 PH according to the instrument set-up)
Hz
kW total (3 PH, 2 PH or 1 PH according to the instrument set-up)
kVA total (3 PH, 2 PH or 1 PH according to the instrument set-up)
PF total (3 PH, 2 PH or 1 PH according to the instrument set-up)
Pressing the PAG key enables to go to the measure selection page corresponding to output 2.
[Fig.5 VIP396 4-20mA 485]
Output 2 measure selection
Pressing the SET key enables to select the same measures set for output 1.
Pressing the PAG key enables to go to the output 1 end value set-up page.
[Fig.6 VIP396 4-20mA 485]
Output 1 end value set-up
Pressing the SEL key enables to select the exponent or digit to modify.
Pressing the SET key enables to modify the selected exponent or digit.
E.g.:
20mA = 20 kA
Pressing the PAG key enables to go to the output 2 end value set-up page.
[Fig.7 VIP396 4-20mA 485]
Output 2 end value set-up
The programming procedure is the same as the output 1 end value programming.
E.g.:
20mA = 150 kVA
The PAG key enables to return to the measurement page.