![Elcontrol STAR 3 User Manual Download Page 13](http://html.mh-extra.com/html/elcontrol/star-3/star-3_user-manual_2377513013.webp)
Page M1 (page and subpages not available in 1PH mode)
Phase-neutral voltages
VL1-N, VL2-N, VL3-N
(3 PH-N, 3 PH )
Phase-neutral voltages
VL1-N, VL2-N
(2 PH)
·Page M1-S1 ( page appearing only in 3PH-N and 2 PH)
Phase to Phase Voltage
VL1-L2
·Page M1-S2 ( page appearing only in 3 PH-N)
Phase to Phase Voltage
VL2-L3
·Page M1-S3 ( page appearing only in 3 PH-N)
Phase to Phase Voltage
VL3-L1
·Page M1-S4 ( page appearing only in STAR HARMO. VL1 has to be connected)
Harmonics Voltages
VL1h, VL2h, VL3h
Use the key SEL to scroll all the harmonics orders h .
The maximum order is depending on the fundamental. It is the 25th at 50 Hz
The voltage input are not connected the harmonics menu does not appear.
·Page M2 (page and sub pages not available in 1PH)
Phase currents
A
L1
, A
L2
, A
L3
(3 PH-N, 3 PH)
Phase currents
A
L1
, A
L2
(2 PH)
·Page M2-S1 (present only in three 3PH-N; 3PH)
Neutral current
A
neutral
·Page M2-S2
Average Phase currents
AL1
Avg
AL2
Avg
, AL3
Avg
The integration time is the same used for the Average power and it is
adjustable into the setup menu.
·Page M2-S3
Phase current peaks
AL1
peak
, AL2
peak
, AL3
peak
maximum average currents.
·Page M2-S4 (Page appearing only in STAR3 HARMO )
Harmonics Currents
AL1
h
, AL2
h
, AL3
h
Use the key SEL to scroll all the harmonics orders h .
The maximum order is depending on the fundamental. It is the 25th at 50 H
·Page M3 (page not available in 1PH)
Phase active powers (kW)
P
L1
, P
L2,
P
L3
(3 PH-N, 3 PH)
Phase active powers
P
L1
, P
L2
(2 PH)
·Page M4 (page not available in 1PH)
Phase Apparent powers (kVA)
S
L1
, S
L2
, S
L3
(3 PH-N, 3 PH)
Phase apparent powers
S
L1
, S
L2
(2 PH)
·Page M5 (not available in 1PH)
Phase reactive powers (kVAr)
Q
L1
, Q
L2
, Q
L3
(3 PH-N, 3 PH)
Phase reactive powers
Q
L1
, Q
L2
,
(2 PH)
·Page M6 (not available in 1PH)
Phase Power Factor
PF
L1
, PF
L2
, PF
L3
(3 PH-N, 3 PH)
Phase reactive powers
PF
L1
, PF
L2
,
(2 PH)
·Page M7
Average Total Harmonic Distortion Factors
Avg THDV=
(THDV
L1
+THDV
L2
+THDV
L3
)/3;
Avg THDA=
(THDA
L1
+THA
L2
+THDA
L3
)/3
These special parameters allow to identify immediately if one of the phases is distorted
.Page M7-S1 (not available in 1PH mode)
Phase THD V
THDV1, THDV2 ; THDV3
(3 PH-N, 3 PH)
THDV1,THDV2
(2 PH)
e.g.: THDV1
=
·Page M7-S2 (not available in 1PH mode)
Phase THD A
THDA1, THDA2 ; THDA3
(3 PH-N, 3 PH)
THDA1, THDA2
(2 PH)
e.g.: THDA1=
rms
h
h
V
V
1
1
25
2
2
=
å
=
ç
è
æ
÷
ø
ö
=
fnd
rms V
V
1
1
(
2
2
-
rms
V
1
rms
h
A
2
=
÷
ø
rms
A
1
h
A
25
2
1
ö
ç
è
æ
å
=
fnd
rms A
A
2
2
1
1
(
-