Closing the "Setting with flame" menu
The burner setting is now complete. It is still possible, however, to correct the individual values.
To do this, position the cursor on the value to be modified, using the
or
key.
At any time, the following options can always be used to close the
"Setting with flame"
menu:
- Restart the burner setting procedure, passing through the presetting phase (without entering a
password). To do this, position the cursor on the symbol
and confirm with the
key. All
the setting values already saved remain available. This is especially essential for testing a new
ignition position.
- Save the specified values and end the setting procedure
.
To do this, position the cursor on the
symbol
and confirm with the key.
Confirm and close the selected settings with symbol
.
Manual Handshake
You are now asked to confirm the modifications that have been made.
Accept or cancel the entry
- The burner is now ready to operate and can be immediately controlled by the boiler regulation.
- Exit the settings menu without reaching the end of the setting procedure. To do this, position
the cursor on the symbol
and confirm with the
key. All the servomotor positions saved
up to this point are recovered by calling up the settings menu again.
Take care with dual fuel burners. The limits for low load and high load apply to both gas and fuel
oil operation. It is not possible to define the different limits for fuel oil and gas. If, for example, the
values are modified during gas mode, these values are also modified automatically for fuel oil
mode.
If values have already been defined, the values for the limits of low and high loads previously
specified for the other fuel are displayed in the menu point (left image).
If the values are modified, they must be confirmed for both fuels.
Operating mode - Display of the operating status, the flame signal and the operating time
Once setting of the burner has been completed, it switches to operating mode.
The current operation of the burner (operation at min. output, medium output or max. output) is
indicated by the cursor.
When ionisation is employed for flame monitoring (gas operation only), the strength of the signal
is shown at the bottom of the display. The possible display range is between 0 μA and 30 μA. A
good quality signal is one that is above < 9 μA in all load points.
If ionisation is not employed for flame monitoring, either 0% or 100% is displayed.
0% - there is no flame signal
100% - there is a flame signal
If O2/CO regulation is employed, the current O2 value can be read in the bottom right-hand corner
of the display.
Commissioning
Menu 1: setting the servomotors
Setting with flame
Operating mode