03/2005 - Art. Nr. 13 018 069A

VECTRON G 03.200 DUO
VECTRON G 03.240 DUO
VECTRON G 03.300 DUO

Betriebsanleitung

Für die autorisierte Fachkraft

Gasgebläsebrenner .............................2-18

Operating instructions

For the authorized specialist

Gas burners .......................................19-35

EN

DE

Ersatzteilliste
Spare parts list
Pièces de rechange
Wisselstukkenlijst .............................37-44

Elektro- und Hydraulikschema
Electric and hydraulic diagrams
Schémas électrique et hydraulique
Elektrische en hydraulische schema ...45-48

Summary of Contents for VECTRON G 03.200 DUO

Page 1: ...rte Fachkraft Gasgebl sebrenner 2 18 Operating instructions For the authorized specialist Gas burners 19 35 EN DE Ersatzteilliste Spare parts list Pi ces de rechange Wisselstukkenlijst 37 44 Elektro u...

Page 2: ...s d rfen nur Dichtungsmaterialien verwendet werden die DVGW gepr ft und zugelassen sind Dichtheit der Ver bindungsstellen mit schaumbildenden Mitteln oder hnlichen die keine Korrosion verursachen pr f...

Page 3: ...erungsautomat SG 513 Flammenw chter Ionisationssonde Z ndtransformator EBI 1 x 11 kV Luftdruckw chter LGW3 A2 Schalldruckpegel nach VDI2715 dB A 68 69 72 Max Umgebungstemperatur 60 C Das Regelverh ltn...

Page 4: ...tung einschlie lich Armaturen Kugelhahn TAS zus tzliche Filter oder Z hler zu ber cksichtigen G 03 200 DUO Brennerleistung kW MBZRDLE 407 B01 S20 Erdgas E Hi 10 365 kWh m 3 Erdgas LL Hi 8 83 kWh m 3 F...

Page 5: ...enschild 8 Brennerrohr 9 Zugsicherung Elektroanschluss 10 Elektroanschluss 4 polig 10 1 Elektroanschluss 7 polig Temperatur regler 16 Gasarmaturanschlussflansch 18 Abdeckhaube 19 Entriegelungsknopf 11...

Page 6: ...ierschraube l sen Achtung entgegengesetzte versiegelte Schraube darf nicht gel st werden Gasdurchsatz vermindern durch Linksdrehen des Einstellknopfes C der sich am oberen Teil der Magnet spule befind...

Page 7: ...sationsstrom muss min 8 A betragen Sicherheitsfunktionen Bildet sich beim Start des Brenners Gasfreigabe keine Flamme so wird nach Ablauf der Sicherheitszeit von max 3 Sekunden der Brenner abge schalt...

Page 8: ...n Span nungsausf llen nicht gef hrdet Wenn die Netz spannung unter dem geforderten Mindestwert liegt schaltet der Automat ohne ein Fehlersignal ab Nach Wiedererreichen einer normalen Spannung l uft de...

Page 9: ...zu am entsprechenden Steckplatz Kunststoffabdeckung mit Hilfe eines kleinen Schraubendrehers abbrechen dann Kabel in Richtung Strangaus gang stecken siehe Bilder 20 21 10 1 8 4 24 2 11 22 6 5 23 4 25...

Page 10: ...des SM Steckers und Phase der Ventil 2 7 Klemme T2 am Wiel Stecker 7P 35 Klemme B4 am Wiel Secker 7P 5 des SM Steckers und Phase der Ventil 1 Klemme 5 des Automaten 9 Klemme 9 des Automaten durch Br...

Page 11: ...wie im nebenste henden Bild erforderlich Die Ausmaue rung darf die Flammrohrvorderkante nicht berragen und mit maximal 60 konisch zulaufen Der Luftspalt zwischen Ausmauerung und Brennerrohr ist mit ei...

Page 12: ...ung der brennstoff hrenden Leitungen Offene Abgaswege ausreichende Frischluftzufuhr Pr fung des Brenner Programmab laufes vor der ersten Gasfreigabe Handabsperrventil vor der Gas Kom pakteinheit schli...

Page 13: ...llung auf Fl ssiggasbetrieb St tzgasblende 3 und Stauscheibe 4 demontieren Zwischenst ck 5 mit Geh use geliefert montieren Stauscheibe 4 und St tzgasblende 3 wieder montieren Montage Mischeinrichtung...

Page 14: ...I muss zwischen Schaltnocke I und IV liegen Die Luftregulierung im Brennkopf beeinflusst neben der Luftmenge auch die Mischzone und den Luftdruck im Brennerrohr Drehen der Schraube A nach rechts mehr...

Page 15: ...n Hand ohne Werkzeug Gasdurchsatz vermindern durch Rechtsdrehen des Ringes D der sich am unteren Teil der Magnetspule befindet Gasdurchsatzvergr sserung durch Linksdrehen 3 ganze Umdrehungen um vom Mi...

Page 16: ...d Vorbel f tung oder Betrieb Luftw chterkontakt unterbrechen Feuerungsautomat muss sofort auf St rung gehen Vor Anlauf Luftdruckw chter berbr cken Brenner schaltet f r ca 2 3 sec ein anschlie end erfo...

Page 17: ...der die Feuerraumt r zu ffnen oder den Brenner auszubauen 1 Zugang ber die Feuerraumt r Die drei Schrauben V auf TF l sen Das Flammrohr nach vorne heraus ziehen Flammrohr wieder montieren Zwischenraum...

Page 18: ...ruckw chter berpr fen oder Gaskompakteinheit austauschen Luftdruckw chter einstellen austauschen Thermostate einstellen oder austauschen Brenner startet bei Einschaltung ganz kurz schaltet ab und gibt...

Page 19: ...l seals and sealing material used must be DVGW tested and approved Check seals and connection points for possible leaks with a suitable non corrosive foam product Bleed the gas conduit before using fo...

Page 20: ...ol unit SG 513 Flame monitor Ionisation probe Ignition transformer EBI 1 x 11 kV Air pressure switch LGW3 A2 Sound level conforms to VDI2715 dB A 76 77 80 Max ambient temperature 60 C The control rati...

Page 21: ...to account the resistance of the burner feed conduit and its fittings ball valve TAS additional filter or meter G 03 200 DUO Burner power kW MBZRDLE 407 B01 S20 Nat gas E Hi 10 365 kWh m 3 Nat gas LL...

Page 22: ...tube 9 Fuse for electrical connection 10 Electrical connection 4 pole 10 1 Electrical connection 7 pole Temperature controller 16 Gas valve assembly connection flange 18 Cover 19 Reset button 113 Air...

Page 23: ...and index x Adjust provisionally to minimum setting Adjustment of throughput stage 2 Loosen locking screw IMPORTANT The counter locked sealed screw MUST NOT be loosened Reduce gas throughout by antic...

Page 24: ...e burner The ionisation current must not drop below 8 A Safety functions If no flame appears when the burner starts up release of gas a safety period of up to three seconds elapses before the burner s...

Page 25: ...controlled program sequence ensures the maximum consistency of the time periods involved regardless of fluctuations in the power supply voltage or ambient temperature The design of the control unit p...

Page 26: ...ollows Use a small screwdriver to snap off the plastic cover over the corresponding plug socket Insert the cable towards the retainer outlet see illustrations 20 21 10 1 8 4 24 2 11 22 6 5 23 4 25 26...

Page 27: ...se of valve 2 7 Terminal T2 at Wiel plug 7P 35 Terminal B4 at Wiel plug 7P 5 of SM plug and phase of valve 1 terminal 5 of control unit 9 Terminal 9 of control unit via bridge or temperature control r...

Page 28: ...he brickwork must not protrude beyond the leading edge of the flame tube and should have a maximum conical angle of 60 The space between the brickwork and burner should be filled with an elastic non i...

Page 29: ...t supply of fresh air Testing of burner program sequence before releasing gas for first time Close manual shutoff valve upstream of gas valve assembly If gas pressure upstream of valve assembly is ins...

Page 30: ...r specifications given Conversion to propane gas operation Remove gas diffusor 3 and turbulator 4 Fit distance piece 5 supplied with burner body Refit turbulator 4 and gas diffusor 3 Fitting burner he...

Page 31: ...air is regulated at two points On the pressure side by means of the opening gap between the turbulator and burner tube On the suction side by means of the air flap actuated by servomotor Y10 Suction s...

Page 32: ...hroughput rate for stage 1 Manually without use of tool Reduce gas throughout by clockwise rotation of ring D located on bottom section of magnet coil Turn anticlockwise to increase gas throughput thr...

Page 33: ...g contact during preliminary ventilation or operation Control unit should go into fault mode IMMEDIATELY Bypass air pressure switch before startup Burner activates for approx 2 3 sec before carrying o...

Page 34: ...t of the flame tube To carry out this procedure the furnace door must be opened or the burner removed 1 Access via furnace door Loosen the three screws V on TF Remove the flame tube by pulling it towa...

Page 35: ...place compact gas fired unit Readjust or replace air pressure switch Readjust or replace thermostat Burner activates briefly at startup then shuts down and emits following signal x x y y y y y y y y C...

Page 36: ...03 2005 Art Nr 13 018 069A 36...

Page 37: ...echange Ersatzteilliste Wisselstukken Spare parts list VECTRON G 03 200 DUO VECTRON G 03 240 DUO VECTRON G 03 300 DUO G 03 200 DUO KN KL 13 011 978 13 011 979 G 03 240 DUO KN KL 13 011 980 13 011 981...

Page 38: ...03 2005 Art Nr 13 018 069A 38...

Page 39: ...3 13 010 014 13 010 013 13 010 014 21 1 Prise C 3P c ble moteur Kabel m Stecker Motor Stekker cable motor Plug cable motor 13 010 519 13 010 519 22 Condensateur 20 2 F 430V 24 30 6 F 400V Kondensator...

Page 40: ...n 5 9 13 007 808 13 003 695 Passe fil ionis 4 9 jaune T lle Ionis Geleider ionisatie Funnel ionisation 13 010 027 13 010 027 58 Vernier quip Regulierknopf Set Set instelknop Setting knob 13 007 852 13...

Page 41: ...41 03 2005 Art Nr 13 018 069A...

Page 42: ...03 2005 Art Nr 13 018 069A 42...

Page 43: ...Prise de pression R1 8 Messnippel m Dichtung R1 8 Meetnippel met afdichting R1 8 Measuring nipple R1 8 13 009 722 146 810 4843 467 2 Bride 407 Rp 3 4 412 Rp 1 1 4 Flansch Flens 13 010 074 13 010 085...

Page 44: ...intenance parts ELCO s performance warranty for them over time under commercial conditions does not apply Les pi ces d entretien sont des pi ces qui devraient tre remplac es titre pr ventif au cours d...

Page 45: ...ydraulic diagrams Sch mas lectrique et hydraulique Elektrische en hydraulische schema VECTRON G 03 200 DUO VECTRON G 03 240 DUO VECTRON G 03 300 DUO G 03 200 DUO KN KL 13 011 978 13 011 979 G 03 240 D...

Page 46: ...r U V D C e l l u l e U V D C e l l U V D F o t o c e l U V D D u r c h l B e l f t u n g V e n t i l p e r m C o n t i n u o u s v e n t i l V o o r t d u r e n d e v e n t i l 4 2 4 2 3 1 0 2 1 2 0...

Page 47: ...B u r n e r A 5 1 8 2 A 1 S G 5 X X G a s s t r a s s e R a m p e g a z G a s v a l v e u n i t G a s v e r d e e l b u i s X 3 B X 3 S M I N K o m p a k t e i n h e i t U n i t c o m p a c t e G a s...

Page 48: ...r m o t o r t r a n s f o r m e r O n t s t e k i n g s t r a n s f o r m a t o r B 1 E l e c t r o d e d i o n i s a t i o n I o n i s a t i o n s e l e k t r o d e e l e c t r o d e I o n i s a t i...

Page 49: ......

Page 50: ...03 2005 Art Nr 13 018 069A 50...

Page 51: ...51 03 2005 Art Nr 13 018 069A...