11
Error reports / Maintenance
Error reports
An error has been detected in the
facility, when this symbol is shown.
Detailed information is available by
pushing the information button.
Error reports / Maintenance
In exceptional cases, one of the
following symbols will be displayed in
the default display:
Maintenance or special mode
When this symbol is displayed, then
a maintenance report is displayed
or the facility is in special mode.
Detailed information is available by
pushing the information button.
Text3
Text4
30:Vorlauffühler 1
0
4
8
12
16
20
24
AUTO
Fehler
Text3
Text4
3:Wartungsintervall
0
4
8
12
16
20
24
AUTO
Wartung
Display lists
Error code
Maintenance code
Error code
Description of the error
0
No entry in Albatros code
10
Weather sensor defect
20
Boiler temperature 1 - sensor defect
32
Inlet temperature 2 - sensor defect
40
Outlet temperature 1 - sensor defect
50
DHW temperature sensor / thermostat 1 defect
52
DHW temperature sensor / thermostat 2 defect
61
Room unit 1 defect
62
Room unit 1 wrong type
78
Water pressure sensor defect
81
LPB short-circuit or no communication
82
LPB address collision
92
Equipment electronics error
105
Maintenance report
110
Safety temperature limiter defect deactivation
117
Water pressure too high
118
Water pressure too low
119
Water pressure switch triggered
121
Inlet temperature heating circuit 1 not reached
122
Inlet temperature heating circuit 2 not reached
128
Flame failure during operations
132
Safety deactivation of gas pressure switch, due to waste gas thermostat
or gas pressure monitor
133
Safety time limit for flame combustion exceeded
151
LMS 14… internal error
152
Parameterization error
153
Facility manually locked
154
Plausibility criteria infringed
160
RPM threshold of blower not reached
161
Maximum blower RPM exceeded
180
Chimney sweep function is active
181
Control unit stop function is active
182
Sitherm Pro electrode drift test is active
184
Modem function is active
185
Attic drying function is active
Maintenance
code
Maintenance description
1
Burner maintenance (burner operating hours)
2
Burner maintenance (burner starts)
3
Burner maintenance (General time interval: Months of service)
5
Lower pressure limit
Summary of Contents for THISION S Combi
Page 20: ...20 Service www elco net ELCO GmbH Hohenzollernstra e 31 D 72379 Hechingen...
Page 40: ...20 Service www elco net ELCO GmbH Hohenzollernstra e 31 D 72379 Hechingen...
Page 60: ...20 Service www elco net ELCO GmbH Hohenzollernstra e 31 D 72379 Hechingen...
Page 80: ...20 Service www elco net ELCO GmbH Hohenzollernstra e 31 D 72379 Hechingen...
Page 100: ...20 Service www elco net ELCO GmbH Hohenzollernstra e 31 D 72379 Hechingen...