Page 6 of 33
1.5
Available flue systems per boiler
Concentric Flue (mm)
Plastic Single Pipe Flue (PPs) (mm)
Thision S Plus
80/125
100/150
Thision S Plus
80 100
110
125
130
34
34
46
46
54
54
Thision L Evo
80/125
100/150
Thision L Evo 80 100
110
125
130
60
60
70
70
80
80
100
100
120
120
140
140
Thision L Eco
80/125
100/150
Thision L Eco 80 100
110
125
130
70
70
100
100
120
120
2. Design and sizing information
2.1 Boiler maximum flue lengths
Thision S Plus
Maximum length in metres for concentric room sealed installations
80/125
100/150
Changes of
direction
0
2
3
4
0
2
3
4
34
25
13.6
7.9
2.2
40
34.2
31.3
28.4
46
12
30
19.4
14.1
8.8
54
11
30
15.4
8.1
0.8
Maximum length in metres for single pipe open or room sealed installations
80mm
100mm
Changes of
direction
0
2
3
4
0
2
3
4
34
30
22
18
14
80
77.1
75.7
74.3
46
12
55
49.9
47.3
44.7
54
11
50
42.9
39.3
35.8