ENTER IN THE SETUP 
From the measures visualization, press at the same time the 

and 

keys, the message SeT  Up  will appear on the 

displays. 

CHOOSE THE DIGITAL OUTPUT TO PROGRAM 
Press repeatedly the 

key until the message SET   DO1  (DO1 output) or SET   DO2  (DO2 output) appears on the 

F

 

display. Press the 

key to select this setting. 

SELECT THE MODALITY OF FUNCTIONING OF THE DIGITAL OUTPUT 
To select the functioning mode, using the 

and 

keys, it’s possible to select: PULSE (pulse emission), ALR   SYS 

3PH, (alarm on three phase value), ALR   PH_ 123 (alarm on minimum and maximum single phase value) and 
BY_  REMOTE  (the digital output is managed using serial output). Press 

key to confirm. 

CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT 
With an alarm modality set, it’s necessary to select the parameters associated to the alarm output; by pressing the 

B

 

and 

keys until the parameter choice appears on the third part (L3) of 

display and the glowing the corresponding 

led on the 

bar. Press 

key to confirm the set. 

SET THE HIGH AND THE LOW THRESHOLDS 
On 

display will appear the message ALR   Hi  with the high threshold value; confirming with the 

key on the same 

display will appear the message ALR   LO  with low threshold value. The 

(to increase) and 

(to decrease) keys are 

used to set the high and the low thresholds values. The range depends by the parameter and it is linked to the CT and 
VT ratios. Pressing 

key to confirm. 

The threshold set is linked with CT and VT ratios, for this reason it’s necessary to make this operation after the 
programming of the CT and VT. The end scale value must be confirmed when CT and VT ratios are modified. 
The low threshold will be lower than high threshold. If the high threshold is set as OFF the low threshold will have the 
range of the high threshold. 
SET THE DELAY TO THE DIGITAL OUTPUT ACTIVATION 
Now it’s possible to set the delay that will pass between the alarm condition set and the activation of digital output. On 

display will appear ALR   DLY  and the value expressed in seconds (range 1÷900). The modification of the value is 

done in the same way of the threshold set. With the confirmation (

key) the set is complete. 

The programming will be referred to the digital output indicated on 

display (DO1  o DO2). 

Summary of Contents for ELM-4D1P

Page 1: ...485 and with analog output OPTIONS Power Supply 20 60 Vac 24 72 Vcc C1 Power Supply 85 230 Vac 90 250 Vcc C2 Insulated current inputs T MEASURED PARAMETERS parameters unit of measurement initial ident...

Page 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 0 230V 220 240Vac 50 60Hz 19 23 0 400V 380 415Vac 50 60Hz 19 21 20 60Vac 24 7...

Page 3: ...WIRING DIAGRAMS W ELM 4D1P instruction manual IM443 U v0 7 pag 3...

Page 4: ...internalCT S1 I1 S2 auxiliary power supply S1 I2 S2 S1 ELM I3 S2 VL1 VL2 VL3 N with Ineutral option In VL1 VL2 VL3 N L1 S1 L2 P1 L3 S1 S2 L1 L2 L3 S1 S2 N P1 P2 P1 P2 CT connection to Voltage insertio...

Page 5: ...lay indicates also the values of the active and reactive energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical m...

Page 6: ...ynchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase f...

Page 7: ...of the CT rate will be possible to set this value example with CT 1000 5the value will be 200 Pressing the A key confirm and go away with the next setting Programming of the average time seT AVG T Aft...

Page 8: ...e password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the set...

Page 9: ...tput will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the...

Page 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Page 11: ...ing the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will...

Page 12: ...key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO P...

Page 13: ...the measures appear on the L1 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltage va...

Page 14: ...er maximum three phase powers max maxD avg I L1 max avg I L2 max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg W max avg...

Page 15: ...electrically disturbed it is suggested to use 100 120ohm 1 2W resistors placed between the common of the RS485 outlet and the shielded cable For other information on the serial line it s better to se...

Page 16: ...auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse P...

Reviews: