LPGas is extremely cold when released to the air (depressurized).

          

Local laws and code of practice regarding LPGas handling as well as instructions of vehicle, 

dispenser and authorized personnel must be followed. Please also refer to the safety codes  

NFPA 54 + 58 and NPGA 306. 

INSTALLATION

The ZVG 2 EURO UL is delivered ready for use. 
Nozzles should only be installed and tested by competent personnel. Applicable laws, regulations 

and Codes of Practice have to be followed. 
Do not use PTFE sealing tape for sealing threaded connections, as electrical conductivity may be 

insufficient and particles of the tape commonly become loose and could clog the nozzle strainer 

or damage vehicle motor parts. Use suitable liquid seal (non permanent) instead.

         Do  n o t  use PTFE tape 

 

   Use liquid seal (non permanent)

After connecting to the hose assembly, an operational test shall be performed. It is essential to  

examine that the nozzle, hose connector and swivel are tight under pressure and do not leak –  

e. g. by external application of foaming agents.  
 

         Assemble with spanners 

 

   Check tightness

3

Summary of Contents for ZVG 2 EURO UL

Page 1: ...ralia Tel 61 2 8058 9258 info elaflex com au www elaflex com au INSTALLATION AND OPERATING MANUAL ZVG 2 EURO UL LPGas Nozzle with EURO Connector 9 2018 Underwriters Laboratory listed Meets EN 13760 UN R 67 ISO 19825 Picture shows optional Scuffguard Nozzle Talker EA 866 ...

Page 2: ...ation tempera ture range 40 F 40 C to 131 F 70 C Test pressure 544 psi 37 5 bar burst pressure in excess of 1450 psi 100 bar Each nozzle is factory tested before being labelled with the prescribed marking production date and unique serial number GENERAL INFORMATION ABOUT LPG WARNINGS LPGas is liquefied under pressure when transported and stored It is heavier than air Commercial LPGas is odourised ...

Page 3: ...odes of Practice have to be followed Do not use PTFE sealing tape for sealing threaded connections as electrical conductivity may be insufficient and particles of the tape commonly become loose and could clog the nozzle strainer or damage vehicle motor parts Use suitable liquid seal non permanent instead Do not use PTFE tape Use liquid seal non permanent After connecting to the hose assembly an op...

Page 4: ...ehicle fill point OFF Fueling will now usually start If leakage is observed release lever to stop process Do not lean on tilt the nozzle On completion of refueling release lever to disconnect If latch is fitted squeeze lever and latch will automatically release During lever release a quantity of liquid gas is discharged from front of the nozzle If the vehicle is equipped with an integrated EURO co...

Page 5: ... release to the atmosphere occurs immediately stop fueling If the leakage continues push emergency button of dispenser leave area and inform station personnel If area is safe check tight connection between vehicle connection and ZVG 2 EURO UL nozzle and coupling Check seals of vehicle connection and ZVG 2 EURO UL coupling If the problem persits notify the station personnel or the service contracto...

Page 6: ...TY LTD has made every effort to explain all servicing procedures warnings and safety precautions as clearly and completely as possible However due to the range of operating environments it is not possible to anticipate every issue that may arise This manual is intended to provide general guidance For specific guidance and technical support contact your authorized supplier Only approved original pa...

Page 7: ...7 ...

Page 8: ...8 Complete operating instructions see page 4 of this manual Follow any additional or deviating instructions displayed at dispenser STOP FUELING START FUELING Latching Unlatching ...

Reviews: