background image

3

EKOVENT AB 

We reserve the right to make changes 

2021-03

Product handling on the construction site

Transport

The fire dampers are transported to the 
construction site with a forklift or crane 
with a lifting fork. To avoid damage, they 
must be lifted, not dragged and never lo-
wered hard against the ground.

Reception and inspection 
of the delivery

The fire dampers are inspected imme-
diately when the delivery arrives at the 
workplace. The inspection is to check that 
the delivery corresponds to the order and 
the consignment note. The approved deli-
very is acknowledged on the consignment 
note. Products with defects or defects 
must not be installed. Contact the supplier 
immediately. 

Storage

The storage of materials on the site should 
be planned so that you get the least pos-
sible internal transport. The fire dampers 
must be protected against water and 
always stored in a dry place. Furthermore, 
they must be handled so that no mechani-
cal damage occurs to them. 

Commissioning

The fire dampers must not be put into use 
until the entire installation is in operational 
condition. 

–   Damage due to incorrect transport, 

handling or storage.

–   That the user has failed to inspect, 

maintain and to a reasonable extent 
take care of the equipment.

–   Personal injury or property damage as 

a result of using the product in violation 
of the instructions and specifications in 
this manual.

EKOVENT AB hereby disclaims all responsibility for:

 

EKOVENT:s liability shall be limited to repair 
or replacement of faulty equipment part.

Summary of Contents for EKO-SRB1

Page 1: ...Installation operating and maintenance instructions 2021 03 Fire damper EKO SRB1 ...

Page 2: ...roduct handling 3 General assembly 4 Mounting accessories 5 Installation instructions 5 6 Operation and maintenance 7 Declaration Of Performance 8 Certification 0402 SP Certification Product type description EKO SRB1 Aproval number SC0848 13 Fire classification E 60 ve i o ho i o SC20 000 Owner of place of manufacture EKOVENT AB Vellinge ...

Page 3: ...ntact the supplier immediately Storage The storage of materials on the site should be planned so that you get the least pos sible internal transport The fire dampers must be protected against water and always stored in a dry place Furthermore they must be handled so that no mechani cal damage occurs to them Commissioning The fire dampers must not be put into use until the entire installation is in...

Page 4: ...n al ternative to calculations or to prove that selected solutions meet the set functional requirements is to use P and CE marked products Mounting In order for the P and CE marking to apply assembly must always take place in accordance with the supplied assembly instructions Other details such as flexible wall sleeve and wall to damper caulking are ordered separately The hole size is always the d...

Page 5: ...lation Gipsväggstos EKO GIS_mellanvägg 2013 90 Installation in flexible wall sleeve EKO GIS Mounting instructions EKO SRB1 1 Squeeze the wall sleeve EKO GIS and insert it into the hole 2 Lock the wall sleeve with a sheet metal screw or pop rivets in the overlap EKO SRBG Gipsväggsstos Mont 2013 Plåtskruv eller popnit av stål ...

Page 6: ...hich the hole is made EI 60 2 Mount the damper in the duct No gaps between the damper and the supporting construction Important The smoke damper should always be installed with the blade shaft horizontal Suspension EKO SRB1 Mont schakt 2014 Ø A 55 Fire sealant Fire sealant Duct Duct Duct Duct EKO SRB1 EKO SRB1 The damper blade shaft must always be installed horizontally 3 Mount the thermal sensor ...

Page 7: ... Also check that the corrosion protection is intact Function control Automatic see above Manuell Manual Manual function check can be performed from the central unit menu During installation manual function check can also be performed on the re spective slave unit applies to EKO MKE SKE EKO TME TSE MME SME Manual function check can be done by pressing the test button for automatic function check wh...

Page 8: ...ormity 0402 CPR SC0844 13 Size Type Classification Ø 100 mm till Ø 630 mm Horizontal duct E 60 ho i o S Vertical duct E 60 Ve i o S Classification according to EN 13501 3 Nominal activation conditions sensitivity Sensing element load bearing capacity Sensing element response temperature Pass ISO 10294 4 Response delay reponse time Closure time Pass EN 1366 2 Operational reliability Cycling Pass EN...

Page 9: ...9 EKOVENT AB We reserve the right to make changes 2021 03 Notes ...

Page 10: ...jselgatan 7 235 32 Vellinge Tel 040 42 16 00 www ekovent se info ekovent se REGIONAL OFFICE GÖTEBORG Boråsvägen 5 435 31 Mölnlycke Tel 031 23 07 40 REGIONAL OFFICE STOCKHOLM Vallgatan 9 170 67 Solna Tel 08 508 613 00 ...

Reviews: