Technical data
Supply voltage
AC 220–230 V, 50/60 Hz
Power consumption
80 VA
Alarm outputs
Potential-free break contacts, 230 V, 5 A
Alarm input
10 mA closed position, 1.8 V open position*
EMC
SS-EN50 130-4
Max number of smoke detectors
30
Ambient temperature
0°C to +43°C
Enclosure class
IP 65
Weight
3.0 kg
* Connected contact must be potential-free.
Technical data for Monitoring system EKO-KE8
Measurement data
Function and location of LEDs
Colour
Location Light
Function
Green
1
Non-flashing
Operation/power on
Red
2
Non-flashing
Fire alarm
Yellow
3
Non-flashing
Detector loop error
Yellow
3
Flashing
Damper error
Red/Yellow
2 & 3
Flashing
Service alarm detector
Green
4
Non-flashing
Normal mode
Red
5
Non-flashing
Alarm mode
Red/Yellow/Green 1, 2, & 3
Non-flashing
Night closing dampers
When the system is starting up,
EKO-KE8 detects which damper
inputs are connected.
NORMAL
ALARM/ERROR
2
(Alarm)
3
(Error)
1
(Operation)
4
(Normal)
5
(Alarm/Error)
Test
Reset
EKO-KE8 oval_ text
DAMPER
196
260
124
296
320
EKO-måttdata KE8
EKOVENT AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden
Tel +46 40 42 16 00, [email protected], www.ekovent.com
2020-03
2 (5)