Ekinex EK-HH1-TP Manual Download Page 3

3

Connection of temperature sensors

The connection of the temperature sensors has to be 

done respectively to the following terminal blocks:
• 

3 and 4 (IN1) for fluid delivery temperature (T

D

• 

5 and 6 (IN2) for fluid return temperature (T

R

• 

7 and 8 (IN3) for external air temperature (T

E

)

Connection of power supply

The connection of the 230 Vac 50/60 Hz power supply is 

made with the screw terminals 1 and 2 (L, N) located at 

the bottom front of the device.
Characteristics of the terminals
•  screw clamping of conductors

•  maximum cross section of conductor 2.5 mm²

•  recommended wire stripping approx. 6 mm

• 

torque max 0.5 Nm

Warning!

 Use exclusively NTC temperature sen-

sors 10 kΩ at 25°C (ß = 3435). The maximum di

-

stance between sensors and device cannot be  lon-

ger than 10 m. 

!

L

N

+

-

230 Vac

50/60 Hz

KNX

bus

15

16

POWER AUX

3

4

IN1

5

6

IN2

7

8

IN3

20

21

DO1

22

23

DO2

24

25

DO3

9

10

IN4

11

12

IN5

13

14

AO1

17

18

19

OPEN

CLOSE COM

1

2

L

N

bus KNX

EK-HH1-TP

Mixing group controller

OK

ESC

+

-

Dev.

Line

Area

45

15

16

POWER AUX

3

4

IN1

5

6

IN2

7

8

IN3

20

21

DO1

22

23

DO2

24

25

DO3

9

10

IN4

11

12

IN5

13

14

AO1

17

18

19

OPEN

CLOSE COM

+

-

M

Auxiliary power supply 

(24 Vac or 230 Vac)

COM

OPEN

CLOSE

Servomotor with 0...10 V control signal

The connection of the servomotor is made with the termi-

nal blocks 13 and 14 (AO1).

45

15

16

POWER AUX

3

4

IN1

5

6

IN2

7

8

IN3

20

21

DO1

22

23

DO2

24

25

DO3

9

10

IN4

11

12

IN5

13

14

AO1

17

18

19

OPEN

CLOSE COM

+

-

M

+

Connection of circulating pump 

The connection of the circulating pump is made with the 

terminal blocks 20 and 21 (DO1).

45

15

16

POWER AUX

3

4

IN1

5

6

IN2

7

8

IN3

20

21

DO1

22

23

DO2

24

25

DO3

9

10

IN4

11

12

IN5

13

14

AO1

17

18

19

OPEN

CLOSE COM

+

-

L

N

230 Vac

50/60 Hz

Control

board

T

M

45

15

16

POWER AUX

3

4

IN1

5

6

IN2

7

8

IN3

20

21

DO1

22

23

DO2

24

25

DO3

9

10

IN4

11

12

IN5

13

14

AO1

17

18

19

OPEN

CLOSE COM

+

-

T

E

T

R

Warning!

 The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off. 

!

Connection of servomotor

3 point floating servomotor

The connection of the servomotor is made with the termi-

nals 17, 18 and 19 (CLOSE / COM / OPEN); it is neces

-

sary also the connection of a 230 Vac or 24 Vac auxiliary 

power supply with the screw terminal blocks 15 and 16 

(POWER AUX).

Summary of Contents for EK-HH1-TP

Page 1: ...flow request contact Connection of 230 Vac or 24 Vac external power sup ply for 3 point floating servomotor Two logical functions with 16 objects each Overtemperature heating and undertemperature cooling alarm management Condensation sensor alarm management Monitoring of operating parameters through alphanu REAEKHH1TP Datasheet STEKHH1TP_EN Operation Regulation mode Heating fixed point external co...

Page 2: ...ides must not be accessible For the mounting proceed as follows with the aid of a tool bring the locking device in the fully lowered position a place the upper edge of the rear inner profile on the upper edge of the rail b rotate the device towards the rail c push the locking device upward until it stops d 45 15 16 POWER AUX 3 4 IN1 5 6 IN2 7 8 IN3 20 21 DO1 22 23 DO2 24 25 DO3 9 10 IN4 11 12 IN5 ...

Page 3: ...3 14 AO1 17 18 19 OPEN CLOSE COM M Auxiliary power supply 24 Vac or 230 Vac COM OPEN CLOSE Servomotor with 0 10 V control signal The connection of the servomotor is made with the termi nal blocks 13 and 14 AO1 15 16 POWER AUX 3 4 IN1 5 6 IN2 7 8 IN3 20 21 DO1 22 23 DO2 24 25 DO3 9 10 IN4 11 12 IN5 13 14 AO1 17 18 19 OPEN CLOSE COM M Connection of circulating pump The connection of the circulating ...

Page 4: ...eleases These activities must be carried out according to the design of the building automation system done by a qualified planner Configuration For the configuration of the device parameters the corre sponding application program or the whole ekinex pro duct database must be loaded in the ETS program For detailed information on configuration options refer to the application manual of the device a...

Reviews: