Ekinex EK-CC2-TP Quick Start Manual Download Page 3

3

Connection of outputs (low-consumption LEDs)

1  2  3  4  5  6

 

9  8  7

 

 

10  

 

Block

Mark

Connection

6

+ 5V

LED power supply

7

OUT1

Output LED 1

8

OUT2

Output LED 2

9

OUT3

Output LED 3 *

10

OUT4

Output LED 4 *

*) not present in the EK-CC2-TP version

Warning! 

The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off. 

!

Mounting

The device has degree of protection IP20, and is therefo-

re suitable for use in dry interior rooms. The support EK-

SMG-35 allows the mounting on 35 mm rail in boards or ca

-

binets for electrical distribution.

a) Insert the mounting support into the appropriate shaped profile of the 

interface

c) Once fastened, connect the bus line, the inputs and the outputs

b) Place the support clamping tooth on the top edge of the mounting 

rail and rotate device and support towards the guide until it completely 

engages

Configuration and commissioning

Configuration and commissioning of the device re

-

quire the use of the ETS

®

 (Engineering Tool Software) 

program V4 2.0 or later releases. These activities must 

be carried out according to the design of the building au-

tomation system done by a qualified planner.

Configuration
For the configuration of the device parameters the corre

-

sponding application program or the whole ekinex

®

 pro-

duct database must be loaded in the ETS program. For 

detailed information on configuration options, refer to the 

application manual of the device available on the website 

www.ekinex.com.

Note.

 The configuration and commissioning of KNX 

devices require specialized skills. To acquire these 

skills, you should attend the workshops at KNX cer

-

tified training centers.

i

Product 

code

Application

software

(## = release)

Comm. 

objects

(max nr.)

Group 

adresses

(max nr.)

EK-CC2-TP

APEKCC2TP##.knxprod

93

255

EK-CD2-TP

APEKCD2TP##.knxprod

93

255

EK-CG2-TP

APEKCG2TP##.knxprod

365

365

Commissioning
For commissioning the device the following activities are 

required:
•  make the electrical connections as described above; 

•  turn on the bus power supply; 

•  switch the device operation to the programming mode 

by pressing the programming pushbutton located on 

the front side of the housing. In this mode of operation, 

the programming LED is turned on; 

•  download into the device the physical address and the 

configuration with the ETS

®

 program.

At the end of the download the operation of the device 

automatically returns to normal mode; in this mode the 

programming  LED  is  turned  off.  Now  the  bus  device  is 

programmed and ready for use.
Reset of the device
To reset the device remove the bus connection by ex-

tracting the bus terminal from its seat. Keeping pressed 

the programming pushbutton, reinsert the bus terminal in 

his seat; the programming LED blinks fast. Release the 

programming button and remove the bus terminal again; 

the reset was carried out. Now you need to address and 

configure again the device via ETS.

Warning! 

The reset restores the device back to the 

state of delivery from the factory. The address and 

the value of the parameters set during configuration 

will be lost

.  

!

Marks

•  KNX

•  CE: the device complies with the Low Voltage Directi-

ve (2014/35/EU) and the Electromagnetic Compatibili-

ty Directive (2014/30/EU). Tests carried out according 

to EN 50491-5-1:2010 and EN 50491-5-2:2010

Maintenance

The device is maintenance-free. To clean use a dry cloth. 

It must be avoided the use of solvents or other aggressive 

substances.