Connection of the KNX bus line

The connection to the main and secondary KNX bus lines 

is made with the terminal blocks (black/red) included in 

delivery and inserted into the slots located on the bottom 

part of the front.
Characteristics of the KNX terminal block
•  spring clamping of conductors

•  4 seats for conductors for each polarity

•  terminal suitable for KNX bus cable with single-wire 

conductors and diameter between 0.6 and 0.8 mm

•  recommended wire stripping approx. 5 mm

•  color  codification:  red  =  +  (positive)  bus  conductor, 

black = - (negative) bus conductor

•  Traffic LED main bus line (2) 

- blinking (green): traffic on main bus line 

- off: no traffic on main bus line 

- blinking (red): transmission error

•  Traffic LED secondary bus line (8) 

- blinking (green): traffic on secondary bus line 

- off: no traffic on secondary bus line 

- blinking (red): transmission error

•  Status LED group addresses (3) 

Routing of group telegrams 

- off: main and sub different 

- on (green): filter table active 

- on (green+red): route all 

- on (red): block

•  Status LED physical addresses (9) 

Routing of physical telegrams 

- off: main and sub different 

- on (green): filter table active 

- on (green+yellow): route all 

- on (yellow): block

•  LED red (5) for displaying the active operating mode 

(on = programming mode, off = normal operation 

mode). After receiving the physical address, the line/

area coupler automatically returns from programming 

mode to the normal operating mode.

Mounting

The device has degree of protection IP20, and is there-

fore suitable for use in dry interior rooms. The housing is 

made for rail mounting according to EN 60715 in boards 

or cabinets for electrical distribution. The installation is in 

horizontal position, the correct position is when the KNX 

bus terminals are located at the bottom. For the installa-

tion of the device on the rail proceed as follows:
•  with the aid of a tool bring the locking device in the fully 

lowered position (1);

•  place  the  upper  edge  of  the  rear  inner  profile  on  the 

upper edge of the rail (2);

•  rotate the device towards the rail (3);

•  push the locking device upward until it stops (4).
Before removing the device, be sure the bus terminals 

have been extracted from their slots. Use a screwdriver 

to slide down the locking device and remove the device 

from the rail.

Configuration and commissioning

Configuration  and  commissioning  of  the  device  require 

the use of the ETS

®

 (Engineering Tool Software) program 

V3 or later releases. These activities must be carried out 

according to the design of the building automation system 

done by a qualified planner.
Configuration
For the configuration of the device parameters the corre-

sponding application program or the whole ekinex

®

 pro-

duct database must be loaded in the ETS program. For 

detailed information on configuration options, refer to the 

application manual of the device available on the website 

www.ekinex.com.

Note. When mounting the device in boards and ca-

binets it shall be provided the necessary ventilation 

so that the temperature can be kept within the ope-

rating range of the device.

+

-

a)

Warning! The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off.

bus

status

traffic

GA

function

PA

R

EK-BA1-TP

MAIN

SUB

Line/area coupler

+

-

b)

a) Main KNX bus line

b) Secondary knx bus line

DCEKBA1TP

Warning! In order to supply the KNX bus lines use 

only a KNX bus power supply (e.g. ekinex EK-AB1-

TP or EK-AG1-TP). The use of other power supplies 

can compromise the communication and damage 

the devices connected to the bus.