EISENZ SKY-3A User Manual Download Page 7

a) Become familiar with the equipment and its operation.

b) Isolate system electrically.

c) Before attempting the procedure ensure that :mechanical handling equipment 

is available, if required, for handling refrigerant cylinders; all personal protective 

equipment is available and being used correctly; the recovery process is 

supervised at all times by a competent person; recovery  equipment  and  

cylinders conform to the appropriate standards.

d) Pump down refrigerant system, if possible.

e) If a vacuum is not possible, make a manifold so that refrigerant can be 

removed from various parts of the system.

f) Make sure that cylinder is situated on the scales before recovery takes place.

g) Start the recovery machine and operate in accordance with manufacturer's 

instructions.

h) Do not overfill cylinders. (No more than 80 % volume liquid charge).

i) Do not exceed the maximum working pressure of the cylinder,even 

temporarily.

j) When the cylinders have been filled correctly and the process completed, 

make sure that the cylinders and the equipment are removed from site promptly 

and all isolation valves on the equipment are closed off.

k) Recovered refrigerant shall not be charged into another refrigeration system

unless it has been cleaned and checked.

10 LABELLING

Equipment shall be labelled stating that it has been de-commissioned and 

emptied of refrigerant.The label shall be dated and signed.

Ensure that there are labels on the equipment stating the equipment contains 

flammable refrigerant.

11 RECOVERY

When removing refrigerant from a system, either for servicing or 

decommissioning, it is recommended good practice that all refrigerants are 

removed safely. When transferring refrigerant into cylinders, ensure that only

10

appropriate refrigerant recovery cylinders are employed. Ensure that the 

correct number of cylinders for holding the total system charge are available.All 

cylinders to be used are designated for the recovered refrigerant and labelled 

for that refrigerant (i.e. special cylinders for the recovery of refrigerant). 

Cylinders shall be complete with pressure relief valve and associated shut-off 

valves in good working order. Empty recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of 

instructions concerning the equipment that is at hand and shall be suitable for 

the recovery of flammable refrigerants.In addition,a set of calibrated weighing 

scales shall be available and in good working order. Hoses shall be complete 

with leak-free disconnect couplings and in good condition. Before using the 

recovery machine, check that it is in satisfactory working order, has been 

properly maintained and that any associated electrical components are sealed 

to prevent ignition in the event of a refrigerant release. Consult manufacturer if 

in doubt. 

The recovered refrigerant shall be returned to the refrigerant supplier in the 

correct recovery cylinder,and the relevant Waste Transfer Note arranged. Do 

not mix refrigerants in recovery units and especially not in cylinders. 

If compressors or compressor oils are to be removed, ensure that they have 

been evacuated to an acceptable level to make certain that flammable 

refrigerant does not remain within the lubricant. The evacuation process shall 

be carried out prior to returning the compressor to the suppliers. Only electric 

heating to the compressor body shall be employed to accelerate this 

process.When oil is drained from a system,it shall be carried out safely.

Competence of service personnel
General

Special training additional to usual refrigerating equipment repair procedures is 

required when equipment with flammable refrigerants is affected.

In many countries, this training is carried out by national training organisations 

that are accredited to teach the relevant national competency standards that 

may be set in legislation.

11

Summary of Contents for SKY-3A

Page 1: ... Connect or clean the exhaust air hose Reset the temperature Clean the air inlet Room temperature is higher than the setting temperature Electric heating mode Room temperature is lower than the setting temperature Cooling mode The doors or windows are not closed There are heat sources inside the room Exhaust air hose is not connected or blocked Temperature setting is too high Air inlet is blocked ...

Page 2: ...of the refrigerant circuit If the appliance is installed operated or stored in a nonventilated area the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of the refrigerant caused by electric heaters stoves or other sources of ignition VERY IMPORTANT Please do not install or use your mobile air conditioner before you ...

Page 3: ...ply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 12 This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe ...

Page 4: ...l be avoided The area around the workspace shall be sectioned off Ensure that the conditions within the area have been made safe by control of flammable material 1 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flammable atmospheres Ensure that the leak tection equip...

Page 5: ...ystem that there is continuity of earth bonding 2 REPAIRS TO SEALED COMPONENTS 2 1 During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of 6 sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be loca...

Page 6: ...rigerant charge shall be recovered into the correct recovery cylinders The system shall be flushed with OFN to render the unit safe This process may need to be repeated several times Compressed air or oxygen 8 shall not be used for this task Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved then venting to atmosph...

Page 7: ...charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall...

Page 8: ... safety equipment before putting into service b Maintenance Portable equipment shall be repaired outside or in a workshop specially 12 equipped for servicing units with flammable refrigerants Ensure sufficient ventilation at the repair place Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible Discharge capacitors in a way that won t cause...

Page 9: ... cause any spark Remove the refrigerant If the recovery is not required by national regulations drain the refrigerant to the outside Take care that the drained refrigerant will not cause any danger In doubt one person should guard the outlet Take special care that drained refrigerant will not float back into the building Evacuate the refrigerant circuit Purge the refrigerant circuit with nitrogen ...

Page 10: ...humidification and sleep mode the wind speed cannot be adjusted The wind speed will be locked in low wind SLEEP 1 When in cooling mode when press the sleep button to enter sleep mode an hour later the set temperature automatically increase 1 C 2 hours later the set temperature automatically add 2 C 2 When the heating mode when press the sleep button to enter sleep mode an hour later the set temper...

Page 11: ...F Press on off to start up and then press on off to shut down WIND Press the swing wind button to start the swing wind function Press the swing button again and the left and right swing function will be cancelled 19 TEMP Under cooling and heating function set in the range of 16 31 C temperature Every click on the temperature set temperature reduced by 1 C TEMP Under cooling and heating function se...

Page 12: ...unctionality Temperature display conversion Press both the temperature and keys and the display will switch between Fahrenheit and Celsius 21 Operation Introduction Before starting operations in this section 1 Find a place where there is power supply nearby 2 Install the exhaust ducts as shown in the figure below and adjust the positions of the mounting plates and windows 3 Insert the power cord i...

Page 13: ...ctric safety requirements When using functions on cooling and dehumidifying keep an interval of at least 3 minutes between each POWER Power supply meets the requirements The socket is for AC use Do not share one socket with other appliances Power supply is AC220V 50Hz 2 Drainage mode 1 Condensate automatic evaporation drainage The machine can automatically evaporate condensed water and discharge i...

Page 14: ... 8 Fig 9 25 Maintenance Explanations Declaration 1 Before cleaning be sure to disconnect the unit from any electric supply outlet 2 Do not use gasoline or other chemicals to clean the unit 3 Do not wash the unit directly 4 If the conditioner is damaged please contact the dealer or repair shop Fig 10 1 Air Filter If the air filter becomes clogged with dust dirt the air filter should be cleaned once...

Reviews: