background image

 

 

 

 

Page 4 of 12 

Drawing   : - TPC427 
Issue 

: - 2 

Date 

: - 26/08/15 

 
 

SPECIFICATIONS 

    
    

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

"This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The 

refrigeration system is hermetically sealed. 

 

The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac 

Industrial Products Ltd is as follows 

 

R134a – 1300 

R407c – 1610 

 

For type and weight of refrigerant contained in this unit, please refer to the product data label"

 

 

 

M

ODEL

10570RG-US 

H

EIGHT

44” (1115mm) 

W

IDTH

25” (625mm) 

D

EPTH

28” (710mm) 

W

EIGHT

170 lbs (77 Kg) 

A

IRFLOW

350 CFM (600 M3/hr) 

P

OWER 

S

UPPLY

110V/ 60Hz/ 1 ph 

F

INISH

Rotational Moulded 
polyethylene 

O

PERATING 

R

ANGE

33°F – 95°F 

R

EFRIGERANT

R-407c (22.9 oz) 

Summary of Contents for RM4500

Page 1: ...Page 1 of 12 Drawing TPC427 Issue 2 Date 26 08 15 RM4500 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...2 of 12 Drawing TPC427 Issue 2 Date 26 08 15 RM4500 PACKAGE CONTENTS Item Description Quantity 10570RG US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC427 Manu...

Page 3: ...harged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradually reduces the relati...

Page 4: ...igerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data la...

Page 5: ...il ii If the air temperature is above 78 F frost and or droplets of condensed water should cover the entire evaporator coil F When the unit is operated in ambient of less than 59 F a defrost cycle sho...

Page 6: ...he coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring...

Page 7: ...f the internal pipework The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing fu...

Page 8: ...s 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty reversing valve 1 Contact the Factory Se...

Page 9: ...014249 2 X 30 6 Solenoid valve 3020833 1 7 Filter dryer 3020957 1 8 Compressor 3944938 1 9 Solenoid coil 3030453 1 10 Hour meter 3030779 1 11 Run capacitor 3036354 1 12 On Off switch 3035924 1 13 Powe...

Page 10: ...Page 10 of 12 Drawing TPC427 Issue 2 Date 26 08 15...

Page 11: ...Page 11 of 12 Drawing TPC427 Issue 2 Date 26 08 15...

Page 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...