CD100E 

INDUSTRIAL DEHUMIDIFIER 

OWNER’S MANUAL 

 
 

 

 

 
 
 
 
 
 
 
 
 

www.eipl.co.uk  

Summary of Contents for CD100E

Page 1: ...Page 1 of 16 Drawing TPC181 Issue 11 Date 24 11 16 CD100E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...e moist room air through the cold evaporator coil which cools the air below its dew point Moisture forms on the evaporator and is collected in the condensate tray then lead away to a permanent drain T...

Page 3: ...sed in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL...

Page 4: ...gle phase fused power supply As follows Brown Live Blue Neutral Green Yellow Earth ground ALARM WIRING Plug L Normally Open Contacts Plug N Close on Humidity Rise Plug E Earth DRAINAGE Connect a 15mm...

Page 5: ...motor is able to take stalled current without burning out the motor windings TEST FOR CORRECT OPERATION 1 Set the adjustment humidistat to maximum 2 Switch the machine to the on position this will re...

Page 6: ...e the build up of ice No attempt should be made to cut open any part of the refrigeration circuit due to high pressures and gas involved If the unit is switched off at the mains power supply for any r...

Page 7: ...he conditions within the area to be dried The following table can be used as a guide APPLICATION HUMIDISTAT SETTING FACTORIES 60 WAREHOUSES 50 BASEMENTS 50 DEFLOODING 40 INDICATOR PANEL The CD100 is f...

Page 8: ...umidistat This humidistat incorporates a knob pointer and a graduated scale which gives the customer the facility to select the desired humidity level within the room being dried The humidistat is pos...

Page 9: ...ve 25 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check al...

Page 10: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 11: ...diagram to find fault and repair Little or no water extraction 1 Insufficient air movement 2 Compressor fault 3 Loss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the F...

Page 12: ...20810 Filter Dryer 3020904 Fan Motor 3030129 Solenoid Coil 3030402 Rotary Switch 3030555 Drain Tube Heater Tape 3031629 Indicator Lamp 3032203 Float Switch 3033021 Contactor 3034389 Panel Mounting Plu...

Page 13: ...12 6 End Cap 13 1 Mounting Fame Assembly 1027301 14 1 Installation Drawing 5060117 Assembly Instructions With reference to the table above unpack the Mounting Frame Kit and check for completeness With...

Page 14: ...e bracket onto the wall 6 Secure the bracket to the wall 7 With reference to Drawing 5060117 Position the CD100 CD100E onto the Wall Mounted Bracket 8 Using Item 6 assemble items 1 and 2 ensuring the...

Page 15: ...d This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products man...

Page 16: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...