2.3  PREPARING THE ENCLOSURE 

To mount the 400 Btu unit you will need to cut an opening in your enclosure and drill 

mounting holes.  A cut out drawing (Fig. 2.3) showing the cut out size and hole locations has been 
included in this manual (see Fig. 2.3).  You also received a cut out stencil with your air 
conditioner.  The instructions for installing the air conditioner are printed below.   

TOOLS AND MATERIALS NEEDED: 

 

AAC-140B-4XT cut out stencil 

 

Center Punch 

 

Tape Measure and pencil 

 

Jigsaw or suitable alternative 

 

Electric drill 

 

# 29 drill bit (.136”) 

 

# 8-32 tap and tap handle 

 

Twelve # 8-32 x 3/8” stainless machine screws (supplied) 

 

Twelve nylon washers (supplied) 

 

One neoprene gasket (supplied) 

 
CUT THE OPENING AND DRILL MOUNTING HOLES IN THE ENCLOSURE 

1.

 

Using the guidelines provided in the installation manual choose an appropriate location for 
the air conditioner on your enclosure. 

2.

 

Tape the cut out stencil to the enclosure in the location you have chosen.   

3.

 

Before marking, cutting or drilling check that the location meets the clearance 
requirements as specified in the installation manual.   

4.

 

Using a pencil, center punch or other method, mark the exact center point of each 
mounting hole on the enclosure.   Also mark the four corners of the section to be cut out. 

5.

 

Remove the stencil and using a pencil or other method, connect the marks you made at the 
corners of the cut out, forming a rectangle. 

6.

 

Using the jigsaw, cut the opening in the enclosure. 

7.

 

Using the # 29 drill bit, drill a hole at each of the mounting hole marks you made earlier. 

8.

 

Using the 8-32 tap, tap each of the holes you have drilled. 

 

2.4  INSTALLING THE AIR CONDITIONER 

INSTALL THE AIR CONDITIONER 

1.

 

Lay the air conditioner down with the cold side fan (side with the thermostat) facing up. 

2.

 

Take the supplied gasket and lay it down on the flange. 

3.

 

Take one of the supplied mounting screws and, from the under side of the flange, push it up 
through the top right mounting hole, and through the hole in the gasket.  The gasket hole is 
undersized and will hold the screw in place.  Repeat this on the top left mounting hole.   

4.

 

Set the AC unit in the hole you’ve cut in the enclosure, and using a screwdriver, carefully 
start the two screws you attached to the gasket to the tapped holes in the enclosure.  Do 
not tighten these at this time. 

5.

 

Install the rest of the screws in the flange placing a nylon washer on each fastener and 
screw them into the tapped holes in the enclosure.  Do not tighten them completely.  If you 
have purchased a vertical drip pan, you will need to install the long screw in the center hole 
in the bottom flange.   

6.

 

Remove the two starter screws and place a nylon washer on each and reinstall. 

7.

 

Tighten all screws. 

Summary of Contents for AAC-140B-4XT

Page 1: ...TIONS INC 215 443 5190 EIC SOLUTIONS INC Thermoelectric Air conditioner installation and operation manual FOR 400 Btu MODEL S AAC 140B 4XT AAC 140B 4XT HC AAC 140B 4XT XXXXX Cooling Solutions for Mission Critical Electronics ...

Page 2: ...PARING THE ENCLOSURE 6 2 4 INSTALLING THE AIR CONDITIONER 6 INSTALL THE DRIP PAN 7 APPLY POWER 8 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 10 3 2 MAINTENANCE 10 EIC SOLUTIONS INC 1825 STOUT DRIVE WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eicsolutions com D 07 Rev D 3 232012 ...

Page 3: ...from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outside...

Page 4: ...or horizontally on the top of your enclosure See Figure 2 1 and 2 2 Vertically mounted 400 Btu units are always mounted with the exposed heatsink fins at the bottom and the fans at the top Fig 2 1 Vertical installations often require the use of a Condensate Drip Pan part DP 140V depending on a number of factors including internal enclosure temperatures and ambient temperatures humidity levels qual...

Page 5: ...F AC INSIDE OF ENCLOSURE DRAIN TUBE ENCLOSURE DP 140V DRIP PAN HOT SIDE FAN COLD SIDE FAN HOT SIDE HEAT SINK FINS COLD SIDE HEAT SINK FINS HORIZONTAL INSTALLATION OF AAC 140B 4XT 400 BTU UNIT WITH INTERNALLY MOUNTED DP 140H DRIP PAN AND DRAIN TUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FAN HOT SIDE FAN COLD SIDE HEAT SINK FINS HOT SID...

Page 6: ...rners of the section to be cut out 5 Remove the stencil and using a pencil or other method connect the marks you made at the corners of the cut out forming a rectangle 6 Using the jigsaw cut the opening in the enclosure 7 Using the 29 drill bit drill a hole at each of the mounting hole marks you made earlier 8 Using the 8 32 tap tap each of the holes you have drilled 2 4 INSTALLING THE AIR CONDITI...

Page 7: ...nstall it on the drip pan Be sure if you use the right angle fitting it is facing the desired direction prior to installing the drip pan 2 There is one mounting hole in the drip pan match this hole with the long mounting screw protruding into the enclosure at the bottom of the AC unit Push the drip pan onto this screw 2 800 3 000 3 000 2 800 2 800 2 800 0 175 0 175 11 250 5 250 ...

Page 8: ...ALLY FIG 2 2 ON THE TOP OF YOUR ENCLOSURE FAILURE TO DO SO MAY ALLOW CONDENSATE TO DRIP IN AN UNCONTROLLED MANNER CAUSING DAMAGE TO YOUR EQUIPMENT APPLY POWER Once the air conditioner is mounted check the serial label and confirm the voltage required and then apply appropriate power as outlined below 120 VAC units plug into standard 120 volt grounded outlet Amperage for a 120 VAC unit is 2 0 amps ...

Page 9: ...hased a Digital Temperature Controller with your AC unit a separate wiring diagram has been provided which will show the correct method of applying power to your particular air conditioner Upon applying power to the air conditioner the fan on the cold side inside the enclosure will come on The hot side fan outside the enclosure may also run depending on where the thermostat is set The cold side fa...

Page 10: ...nit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed using compressed air to blow out the heat sinks Do not direct any high press...