background image

The battery also needs to be replaced if it is over 5 years old (see “replace battery by” date on side
panel). To remove the battery reverse the instructions in the first part of section 2. Contact nearest
address at the end of this leaflet on obtaining a replacement battery.

Replace the entire Strobe Module after 10 years operation. (see “replace unit by” date on side panel).

5. TROUBLESHOOTING

If the units fail any of the above tests after installation, the system has probably been incorrectly
installed and/or all units are not House Coded correctly. Check carefully that all units are powered. If
the power lights on any of the mains units are not on constantly, or flashing once every 45 seconds on
battery powered units, check the connections to the mains and/or the connections to the batteries.
(See individual unit instruction leaflets if necessary). For mains units check that the power is not off
(i.e. due to a tripped circuit breaker or fuse).

There are no user serviceable parts in this unit (apart from the battery). If the unit (apart from the
battery) is thought to be defective, it must be returned to the nearest address at the end of this leaflet
for repair or replacement (see “Five Year Guarantee” section).

Some troubleshooting items (including RF links) are specific to individual units and may not be covered
in this leaflet. In these cases the more comprehensive unit leaflet should be consulted.

6. OTHER FEATURES & ACCESSORIES

OTHER FEATURES

Strobe Module - Auxiliary Outputs - AUX 1 & AUX 2: The two auxiliary outputs are activated when
the Strobe Module is in alarm. The Aux 1 socket can supply up to 180mA at 12 Volts. The AUX 2 socket
can supply up to 20mA at 12 Volts.

N.B. The AUX 2 socket can be used for low power devices such as pager trigger inputs.

Note: As supplied  the two auxiliary sockets AUX. 1 and AUX. 2 are protected by latched  plastic plugs
which must be removed before the auxiliary devices can be plugged in (see figure 5). These plugs can
be removed by pressing the latch lever (on the side nearest the “AUX” marking) before gently pulling
the plug off.

“Clock Input” Socket: (not available without a vibration pad). A suitable alarm clock signal (with a
5 to 24 Volts AC or DC output – electrically isolated from the mains supply) can be connected to this
input socket with a 3.5mm mono jack plug. (see figure 4) When the alarm clock triggers, the vibration
pad turns on continuously (i.e. it is not pulsed) to wake the person, but the internal strobe or auxiliary
outputs are not activated. This lets the user know it is a wake-up call and not a fire. Therefore the user
needs only one vibration pad under their pillow or mattress – rather than two, one for the Fire Alarm
and one for the alarm clock.

ACCESSORIES

Ei178 - Auxiliary Strobe: (draws 180mA). Supplied with 10m of cable and a suitable plug for
connection to the auxiliary socket. It should be plugged into AUX 1. It can be located, for example,
where it is readily seen during the day (e.g. downstairs hallway).

Ei174 - Auxiliary Vibration Pad: (draws 120mA). Supplied with 5m of cable and a suitable plug for
connecting to the auxiliary socket. It should be plugged into AUX 1.

Ei410 - RadioLINK Remote Control (portable)The Remote Control Ei410 allows you to Test, Hush or
Locate suitable RadioLINK Smoke/Fire/Heat Alarms.

Ei411H - RadioLINK Remote Control (wall mounted)This wall mounted switch allows you to Test,
Hush or Locate suitable RadioLINK Smoke/Fire/Heat Alarms. (Note: the Strobe Module Ei170RC
ignores a RadioLINK LOCATE message and will continue to flash the strobe and drive the vibration
pad as long as it gets an RF alarm signal).

Ei407 - RadioLINK Manual Call Point: This allows remote triggering of RadioLINK alarms / accessories
and is ideal where emergency situations are identified and which require immediate evacuation.
Ei428 - RadioLINK Relay Module: This module contains a set of relay contacts that switch upon
receipt of an alarm signal from suitable RadioLINK Smoke/Fire/Heat Alarms.

7

B16566-R0-Ei171RF-ENG-UC  2/9/09  2:54 PM  Page 7

Summary of Contents for RadioLINK Ei171RF

Page 1: ...arm is required to make the Ei171RF Alarm operational This is not supplied with the Ei171RF and must be obtained separately Important Read these instructions together with those from the separate RadioLINK Smoke Heat Fire alarms and accessories before installation All instruction leaflets must be left with the end user after installation Model Ei171RF B16566 R0 Ei171RF ENG UC 2 9 09 2 54 PM Page 1...

Page 2: ... normally be fixed such that the internal strobe light can be seen from the bed An additional strobe module can be then placed in any other living area of the house which can be readily seen by the occupant It has to be powered from the mains 230VAC so a suitable socket or junction box must be available to which it can be permanently connected The back up battery in the Strobe Module must not be e...

Page 3: ...let can be used to locate the screws accurately The screws large heads should be screwed into the wall leaving a gap of approximately 4mm 0 15in under the head Fit the keyhole slots on the back of the Strobe Module over the screw heads and slide the panel down vertically into position The mains adaptor should then be plugged into a socket or permanently wired to a mains junction box see overleaf T...

Page 4: ...so that they will not accidentally signal to or be affected by nearby systems The units will all communicate with each other providing they are within range as delivered i e without any House Coding however it is recommended that they are House Coded as follows 3 1 1 Install power all the elements of the system 3 1 2 Press the House Code switch on all units see individual instruction leaflets for ...

Page 5: ...n as this will put it back into House Code Mode 3 2 ADDING UNITS To add units to the system simply repeat the above procedure i e put all into House Code Mode new as well as old units and ensure that the number of flashes shown equals the number of units in the system For the other RadioLINK components see their instruction leaflets 3 3 RESETTING HOUSE CODES Sometimes it is necessary to cancel the...

Page 6: ...moke Fire Heat alarms and any accessories 4 2 3 Check that the amber fault light is not flashing every 4 seconds If it is check that the conversion jack is connected firmly to the socket with its plug latched see figure 1 If this connection is satisfactory it is probably indicating that the battery is depleted Connect the unit to the mains and check after 24 hours that the amber fault light has ce...

Page 7: ...iary devices can be plugged in see figure 5 These plugs can be removed by pressing the latch lever on the side nearest the AUX marking before gently pulling the plug off Clock Input Socket not available without a vibration pad A suitable alarm clock signal with a 5 to 24 Volts AC or DC output electrically isolated from the mains supply can be connected to this input socket with a 3 5mm mono jack p...

Page 8: ...es to normal conditions of use and service and does not include damage resulting from accident neglect misuse unauthorised dismantling or contamination howsoever caused This guarantee excludes incidental and consequential damage If this device should become defective within the guarantee period it must be returned to the nearest address given below carefully packaged with the problem clearly state...

Page 9: ...mplate for Mounting Screws Drill Holes Here 12V 180mA max Aux1 12V 20mA max Aux2 Conversion Jack Remove protection plug before connecting accessories Figure 5 B16566 R0 Ei171RF ENG UC 2 9 09 2 54 PM Page 9 ...

Page 10: ... battery fully depleted Sensing Fire Fire signal received from Smoke Alarm __ __ __ __ Test Mode Test button pressed on deaf alarm 1 flash 2 sec __ __ __ __ 40 flashes min on for 4 sec flashes on 1 flash 2 sec __ __ __ Test button pressed on deaf alarm Fault Mode Conversion Jack disconnected 40 flashes min on __ __ __ __ __ __ __ __ Battery disconnected mains on House Code Mode for RF Press button...

Page 11: ... Green mains disconnected amber flash 4 seconds RadioLINK Signalling Blue Control Panel Indicators Alarm Red Fault Indicator Amber Strobe TEST ALARM FAULT INDICATOR SUMMARY B16566 R0 Ei171RF ENG UC 2 9 09 2 54 PM Page 11 ...

Page 12: ...s that this product should not be disposed of via the normal household waste stream Proper disposal will prevent possible harm to the environment or to human health When disposing of this product please separate it from other waste streams to ensure that it can be recycled in an environmentally sound manner For more details on collection and proper disposal please contact your local government off...

Reviews: