Return to the Ei450 i-controller and check that all 4 segments
(ring) are flashing blue. The number of flashes should
equal the number of RadioLINK devices in the system.
A system with 3 smoke alarms, one CO alarm and the
i-controller will result in five blue flashes.
The flash pattern will repeat every 5 to 10 seconds while the
i-controller remains in house code.
If it fails to flash the correct number of times, then consult the
“Troubleshooting the RF link” section of this instruction manual.
Now, walk around the house to verify that all the other
RadioLINK Alarms and RadioLINK devices are giving the correct
amount of flashes.
If any of these fail to flash the correct number of times,
then consult the “Troubleshooting the RF link” section of this
instruction manual.
To complete the commissioning, the system must exit house
code mode.