LOW VOLTAGE PANEL SMOKE & HEAT ALARMS

Ei181

Ei184

Ei186

© Ei Electronics 2014

P/N B14090 Rev4

Summary of Contents for Ei 181 Ionisation

Page 1: ...LOW VOLTAGE PANEL SMOKE HEAT ALARMS Ei181 Ei184 Ei186 Ei Electronics 2014 P N B14090 Rev4...

Page 2: ...IS PRESSED FOR 10 SECONDS IF THE UNIT BEEPS EVERY 40 SECONDS FOR OVER 20 MINUTES THE BATTERY IS PROBABLY DEPLETED REMOVE UNIT FROM CEILING SEE FIG 1 AND REPLACE BATTERY DO NOT ATTEMPT TO OPEN THE ALAR...

Page 3: ...he Heat Alarm gives a fire warning when the temperature at the unit reaches 58 C It is ideal for kitchens garages boiler houses and other areas where there are normally high levels of fumes smoke or d...

Page 4: ...of potential sources of fire Single Storey Dwelling If the Home is on one level a bungalow or mobile home for example you should put the first Smoke Alarm in a corridor or hallway between the sleepin...

Page 5: ...he room such as an elderly or sick person or a very young child Fire Authorities including the Home Office UK recommend that both Optical and Ionisation Smoke Alarms should be fitted for the fastest r...

Page 6: ...e attic hatches uninsulated exterior walls etc Temperature differences might stop smoke or heat from reaching the unit Next to or directly above heaters or air conditioning vents windows wall vents et...

Page 7: ...lly see figure 5 because dead air at the apex may prevent smoke from reaching the unit INTERCONNECTING SMOKE HEAT ALARMS When a fire is sensed the alarm must be given throughout the house Up to twenty...

Page 8: ...shing which are causing all alarms to sound INSTALLING SMOKE HEAT ALARMS The Alarm is designed to be permanently mounted using it s own built in terminal blocks to connect it to the panel The mounting...

Page 9: ...MAINS SWITCH with a contact separation of at least 3mm in each pole Installation Select a location complying with the above advice 1 Remove the mounting plate from the Smoke Heat Alarm by releasing t...

Page 10: ...s illuminated on the mounting plate This shows the panel is supplying power Press the test button for up to 10 seconds to ensure the sensor chamber electronics and sounder are working A red light on t...

Page 11: ...red light does not flash at the same time it indicates a problem with the smoke chamber see Cleaning the Smoke Alarm section below If the beeps have continued for over 20 minutes and the other causes...

Page 12: ...rs when needed must be performed by the manufacturer All Alarms are prone to dust and insect ingress which can cause false alarms or failure to alarm The latest design materials and manufacturing tech...

Page 13: ...h Button located on the cover The Alarm will automatically switch to a reduced sensitivity condition very large levels of smoke from a nearby fire will override the Hush on the smoke alarms This condi...

Page 14: ...Test Buttons to familiarize your family with the Alarm sound and to practice fire drills regularly with all family members Draw up a floor plan that will show each member at least 2 escape routes from...

Page 15: ...alling Smoke Heat Alarms on both sides of closed doors and installing more than one Smoke Heat Alarm as recommended in this leaflet very significantly improves the probability of early detection The A...

Page 16: ...in the post State the nature of the fault where the Alarm was purchased and the date of purchase FIVE YEAR PRODUCT GUARANTEE Ei Electronics guarantees this Alarm excluding the battery for five years f...

Page 17: ...ht on mounting plate for panel power Red LED flashes every 40 seconds Alarm output Piezo horn 85dB A 3m Standby Temp 0oC 40oC Humidity 10 90 Relative HumidityInterconnect Up to 20 units in total Ei181...

Page 18: ...10 seconds while in hush At the end of the hush period unit gives a double beep Airspeed No effect Contamination Much less affected by insects and contamination than Smoke Alarms Dimensions 145mm d x...

Page 19: ...s providing power and replacing battery or cleaning unit has not stopped beeps a fault may exist Replace the unit see figure 1 2 The Ionisation Heat units Ei181 180 184 183 give two beeps 10 minutes a...

Page 20: ...Devices Ei184 Fire Safety 0086 Aico Ltd Mile End Business Park Maesbury Rd Oswestry Shropshire SY10 8NN U K Tel 01691 664100 www aico co uk Ei Electronics Shannon Co Clare Ireland Tel 061 471277 www e...